Doc. #
: M1800, Rev. 06
Page 92 of 101
www.opwglobal.com
Combo Dual-Level/Hydrocarbon Liquid Sump
Sensor
OPW P/N: 30-3225
Combo Dual-Level/Hydrocarbon Liquid Sump Sensor
This sensor is made from the Hydrocarbon Liquid Sump Sensor (30-
3219-12) with a Dual-Level Reservoir Sensor (30-3221-2) clipped to
its side. The combination sensor is designed to detect the presence
of liquid hydrocarbons and water in sumps, dispenser pans and other
locations where the presence of a liquid could indicate that a leak has
occurred.
The sensor contains a carbon/polymer material that changes
resistance when exposed to liquid hydrocarbons. The level sensor
portion simply clips onto the hydrocarbon sensor and can be
positioned at any desired height to activate in the presence of liquid.
Combo Dual Level/Hydrocarbon Liquid Sump Sensor
Substances Detected:
Liquid Hydrocarbon and Water
Operating Temperature:
-4°F to 122°F (-20°C to +50°C)
Dimensions:
30-3221-2
30-3219-12
2.4” x 14” (6 cm x 35.6 cm)
1.7” x 13.2” (4.4 cm x 33.5 cm)
Required Cable:
12
’ (3.6 m) of gas-and-oil resistant cable
Maximum Wiring Length*:
1,000’ (305 m)
Nominal resistance
(uncontaminated):
1K - 5K ohms
Nominal resistance
(contaminated):
30K - 200K ohms
Multi-Drop Restriction:
1 per channel
Connections:
Channel 1: Red = Power, White = Signal
Channel 2: Black = Signal
Summary of Contents for OPW SiteSentinel Integra 100
Page 18: ...Doc M1800 Rev 06 Page 18 of 101 www opwglobal com 2 7 Field Wiring Diagram for Integra 100 ...
Page 19: ...Doc M1800 Rev 06 Page 19 of 101 www opwglobal com ...
Page 20: ...Doc M1800 Rev 06 Page 20 of 101 www opwglobal com 2 8 Field Wiring Diagram for Integra 500 ...
Page 21: ...Doc M1800 Rev 06 Page 21 of 101 www opwglobal com ...
Page 48: ...Doc M1800 Rev 06 Page 48 of 101 www opwglobal com 10 3 3 Flex Probe Determination Worksheet ...
Page 52: ...Doc M1800 Rev 06 Page 52 of 101 www opwglobal com Figure 11 4 Tighten Sensor ...
Page 83: ...Doc M1800 Rev 06 Page 83 of 101 www opwglobal com Appendix H Model 924B Installation Records ...
Page 86: ...Doc M1800 Rev 06 Page 86 of 101 www opwglobal com L048 Overall Length ...
Page 99: ...Doc M1800 Rev 06 Page 99 of 101 www opwglobal com Appendix M Declaration of Conformity ...
Page 100: ...Doc M1800 Rev 06 Page 100 of 101 www opwglobal com ...