Doc. #
: M1800, Rev. 06
Page 46 of 101
www.opwglobal.com
10 Flex Probe Installation
10.1 Model 7100V Flex Probe (only for Integra
500)
The 7100V Flex Probe utilizes the same magnetostrictive technology
for above ground tanks up to 70 feet (15.2 m) in height. It is important
to follow the handling instructions to avoid damaging the probe and
voiding the warranty. During the unpacking and installation of the
Model 7100V Flex Probe, always keep the diameter of the coils
between 40 and 48 inches (about 1 m).
Flex Probe Installation Requirement:
Flex probe head/wiring must
be installed in weatherproof junction box with seal packs for wiring
connections. Failure to comply with these requirements may
invalidate probe warranty.
10.2 Model 7100V Flex Probe Specifications
DO NOT
REMOVE
YELLOW
TAG
Figure 10-1 Model 7100V Flex Probe
Summary of Contents for OPW SiteSentinel Integra 100
Page 18: ...Doc M1800 Rev 06 Page 18 of 101 www opwglobal com 2 7 Field Wiring Diagram for Integra 100 ...
Page 19: ...Doc M1800 Rev 06 Page 19 of 101 www opwglobal com ...
Page 20: ...Doc M1800 Rev 06 Page 20 of 101 www opwglobal com 2 8 Field Wiring Diagram for Integra 500 ...
Page 21: ...Doc M1800 Rev 06 Page 21 of 101 www opwglobal com ...
Page 48: ...Doc M1800 Rev 06 Page 48 of 101 www opwglobal com 10 3 3 Flex Probe Determination Worksheet ...
Page 52: ...Doc M1800 Rev 06 Page 52 of 101 www opwglobal com Figure 11 4 Tighten Sensor ...
Page 83: ...Doc M1800 Rev 06 Page 83 of 101 www opwglobal com Appendix H Model 924B Installation Records ...
Page 86: ...Doc M1800 Rev 06 Page 86 of 101 www opwglobal com L048 Overall Length ...
Page 99: ...Doc M1800 Rev 06 Page 99 of 101 www opwglobal com Appendix M Declaration of Conformity ...
Page 100: ...Doc M1800 Rev 06 Page 100 of 101 www opwglobal com ...