Digital Security Controls Ltd.
16
Private and Confidential
Installation Manual
DATE : 09/30/97
DRAFT
The system will use one common exit delay time that must be programmed to accommodate the
longest possible exit time required. The default Exit delay time is 120 seconds.
Bell Cut-off:
(001-255) Minutes
This value determines the time the bell / siren will sound before automatically turning off. The default bell
cutoff time is 4 minutes.
Alarms/Events which cause the Keypad Buzzer to sound (System Tampers, 24 Hour Buzzer Zone, etc)
do not follow this Bell Cutoff Timer. The buzzer will sound until an access code is entered to silence the
condition.
8.2.3 Special Access Codes [006]-[008]
Each of these sections require 4 or 6 digits to be entered.
Installer’s Code.
Master Code.
Maintenance Code
. This is a Arm/Disarm only code. It can not be used to bypass program other user
codes or enter the [*][6] menu. Openings or Closings using this code report as a Special Opening/Closing
and will log to the event buffer as “Maintenance Code”.
8.2.4 Keypad Lockout Options [012]
This section determines how the keypad lockout function operates.
Number of Invalid Codes Before Lockout
Program a number from 000 to 255 to determine the number of invalid master, duress, user or installer
access code entries to reach keypad lockout. When keypad lockout occurs, the system is rendered
inoperative via keypad for the programmed duration. When any keys are pressed, an error tone will
sound. Entering 000 disables the feature.
Lockout Duration
Program a time from 000 to 255 minutes to determine the length of time before lockout resets and the
keypad can once again be used.
Note:
If lockout is not reached within the hour roll-over, the number of invalid attempts is reset
to 0.
FAP keys are still active during Keypad Lockout.
8.2.5 System Options Codes
[013] First System Options Code
[1] Hardwired Zone Supervision Option
ON = Hardwired Zones are EOL
Both hardwired zone loops on the WLS9000 use EOL supervision.
OFF = Hardwired Zones are Normally Closed
Both hardwired zone loops on the WLS9000 use Normally Closed loops.
[2]-[3] Not Used
[4] Tampers/Faults Annunciation Option
ON = Tampers and Faults Do Not Annunciate as Open
The panel will not annunciate the respective Zone if the zone is in the Tamper or Fault states,