8.2.1 Zone Definitions [001]-[004]
Each of these sections require 8 two digit entries. Each two digit number entered describes how a zone will
operate.
00 Null Zone
is for zones that are not used and does not require a closed loop or EOL resistor
01
Delay 1
follows the Entry Delay 1 and Exit Delay programmed in Section
[005] and is normally used for
Entry/Exit doors. The exit delay starts as soon as the panel is armed. The zone may be opened and
closed during the delay time without causing an alarm. After the exit delay time has expired, opening
the zone will start the Entry Delay timer. During the Entry Delay time, the keypad buzzer will sound
steadily to advise the user that the system should be disarmed. If the panel is disarmed before the Entry
Delay expires, no alarm will be generated.
02 Delay 2
operates the same as Type [01] zone except the Entry Delay time can be independently set in
Section [005]. The Exit Delay time is common to both zone types.
03 Instant
is normally used for door and window contacts and has the standard Exit Delay, but is instant when
opened after the Exit Delay expires.
04 Interior
are used with interior motion detectors. Interior zones feature both an Exit Delay and an Entry Delay
provided that any Delay type zone has been tripped first. If the protected area is entered without coming
through the a delayed entrance and an Interior zone is tripped, an immediate alarm will be generated.
05 Interior Stay/Away.
If the system is armed and a Delay zone is NOT tripped during the exit delay time,
this zone type will be bypassed. If the [*][1] command is used to activate all Stay/Away type zones,
this zone will have the standard exit delay. Once armed, this zone will act like an Interior type zone [04].
06 Delay Stay/Away
If the system is armed and a Delay zone is NOT tripped during the exit delay time,
this zone type will be bypassed. If the [*][1] command is used to activate all Stay/Away type zones,
this zone will have the standard exit delay. Once armed, this zone will always have follow the Entry Delay
time for Entry Delay 1 when tripped.
Note: The automatic bypass on Stay/Away type zones will not be removed by any event other
than a valid exit through a Delay type 1 zone during the exit delay or by pressing [*][1] while
armed.
07-08 Not Used
x
10 24 Hour Supervisory Buzzer
is active at all times and will report an alarm at all times. Once tripped, the
keypad buzzer will sound until a valid access code is entered. If configured for Global operation, an
access code will be required on each partition to silence the buzzer on the corresponding partition.
Note: This zone type should not be used on a Keyswitch ONLY system.
11 24 Hour Burglary
is active at all times and will report an alarm if the panel is armed or disarmed. This type
will sound the bell for the length of Bell cutoff if the audible attribute is enabled.
12 24 Hour Holdup
is similar to 24 Hour Burglary except for System Event output type and SIA identifier.
13 24 Hour Gas
is similar to 24 Hour Burglary except for System Event output type and SIA identifier.
14 24 Hour Heat
is similar to 24 Hour Burglary except for System Event output type and SIA identifier.
15 24 Hour Medical
is similar to 24 Hour Burglary except for System Event output type and SIA identifier.
16 24 Hour Panic
is similar to 24 Hour Burglary except for System Event output type and SIA identifier.