5.  Place  flashing  over  pipe  section(s)  ex

-

tending  through  roof.  Secure  base  of 

flashing to roof and framing with roofing 
nails.  Be  sure  roofing  material  overlaps 
top edge of flashing as shown in Figure 

16, page 13. There must be a 1" clearance 
from vent pipe to combustible materials.

6.  Continue to add pipe sections until height 

of vent cap meets the minimum building 
code requirements described in Figure 7 
on page 7.

 

Note: You must increase vent height for 
steep roof pitches. Nearby trees, adjoining 

rooflines,  steep  pitched  roofs  and  other 

similar  factors  may  cause  poor  draft  or 
down-drafting  in  high  winds.  Increasing 
vent height may solve this problem.

7.  Twist-lock  vent  cap  onto  last  section  of 

vent pipe.

Note: If vent pipe passes through any occu-

pied areas above first floor, including storage 

spaces and closets, you must enclose pipe. 
You may frame and sheetrock enclosure with 
standard  construction  material.  Make  sure 
and meet the minimum allowable clearances 

to combustibles. Do not fill any required air 

spaces with insulation.

Vertical Termination Configurations

Figure 18 shows the configurations for vertical 

termination.

ventinG inStALLAtiOn

Continued

Figure 18 - Vertical Venting Configuration

Vertical 
Venting

V = 40' max.

HIGH ALTITUDE INSTALLATION

Your DESA Heating, LLC direct vent fireplace 

has been tested and approved for elevations 

from 0-2000 feet (USA).

When installing at an elevation above 2000 

feet (in the USA), you may need to decrease 

the  input  rating  by  changing  the  existing 

burner orifice to a smaller size. Reduce input 

4% for each 1000 feet above sea level. Check 

with your local gas company for proper orifice 
size identification.
When installing this fireplace at an elevation 

above 4500 feet, check with local authorities.

OUTSIDE AIR FLEX INSTALLATION

Outside air flex installation is required for both 
horizontal  and  vertical  venting  installation. 
There are 2 outside air flex kits available for 

purchase (see 

Parts List for Venting Kits and 

Components

, page 15).

Construct a 8 

1

/

2

" x 8 

1

/

2

" framing or opening 

on exterior wall (see Figure 19). Install outside 

air vent termination in a location that would 
not eventually be obstructed by bushes, snow 
or other obstructions. Locate outside air vent 

near  fireplace  to make  flex  duct  installation 

easier.

Figure 19 - Outside Air Flex Duct 

Installation

Outside Air Vent 
Termination

Flex Venting

Secure Both Ends of 
Flex Using Hi-Temp 
Duct Tape

Summary of Contents for IRONHAUS Yellowstone IDVF36HN

Page 1: ...ierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer serv...

Page 2: ...ful home 1 Inspect your enclosure and fireplace unit for any damage Contact your dealer and or shipper immediately if damaged and document with photos etc 2 Remove handcrafted face and mesh door and s...

Page 3: ...horizontal and vertical installation This fireplace complies with the National Safety Standards This fireplace must be installed by a qualified certified or licensed service person It brings in fresh...

Page 4: ...ected annually by a qualified service person 5 You must keep control compartments burners and circulating air passages clean More frequent cleaning may be needed due to excessive lint and dust from ca...

Page 5: ...in the way of the venting system Choose a location where the heat output is not affected by drafts air conditioning ducts windows or doors Figure 2 shows some common locations Be aware of all restrict...

Page 6: ...or other materials 0 clear ance to combustible materials are for framing purpose only NOTICE Thisfireplaceisintend edforuseassupplementalheat Use this fireplace along with your primary heating system...

Page 7: ...30 cm in US if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m hori...

Page 8: ...ade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than 1 2 in size GAS VENT DIRECTLY B...

Page 9: ...vent pipe components and terminations The venting system must terminate on the outside of the structure and can not be at tached to a chimney or flue system serving a separate solid fuel or gas burnin...

Page 10: ...with special twist lock con nections Twist Lock Procedure Female ends of pipes have locking lugs indentations These lugs will slide straight into match ing slots on male ends of adjacent pipes Push pi...

Page 11: ...rior wall with provided wood screws see Figure 11 Siding standoff must sit flush against exterior fascia material 6 Connecting Vent Cap with Horizontal Vent Pipe Slide wall firestop over vent pipe bef...

Page 12: ...with critical minimum and maximum dimensions which MUST be met NOTICE Donotsealtermination cap to vent pipe Cap must be removable for vent inspection and maintenance WARNING Never run vent downward a...

Page 13: ...If area above ceiling is an insulated ceiling or an attic nail firestop from top side This prevents loose insula tion from falling into required clearance space If area above ceiling is a living space...

Page 14: ...18 shows the configurations for vertical termination Venting Installation Continued Figure 18 Vertical Venting Configuration Vertical Venting V 40 max High Altitude Installation Your DESA Heating LLC...

Page 15: ...Air Flex Vent Kit CHECK GAS TYPE Use proper gas type for the fireplace unit you are installing If you have conflicting gas types do not install fireplace See retailer where you purchased the fireplace...

Page 16: ...g equipment shutoff valve to fireplaces Figure 20 External Regulator with Vent Pointing Down Propane LP Only Propane LP Supply Tank External Regulator with Vent Pointing Down Fireplace Installation Co...

Page 17: ...ff valve was connected 3 Pressurize supply piping system by either opening propane LP supply tank valve for propane LP gas fireplace or opening main gas valve located on or near gas meter for natural...

Page 18: ...to Appliance page 22 Removing Replacing Glass Doors CAUTION Do not operate thisfireplacewithabrokenglass door panel or without the glass door panel securely in place For replacement part informa tion...

Page 19: ...ddle Bottom Brick Right Bottom Brick Glass Door Lava Rock Ember Flakes and Scrap Log Installation Lava rock ember flakes and scrap log pieces are included with your fireplace Install these items while...

Page 20: ...Once battery is activated the unit is ready to use 5 Replace center brick control cover Figure 32 Installing Battery into Back of Handset Battery Cover Back of Handset Fireplace Installation Continue...

Page 21: ...fety information col umn 1 2 Turn off all electric power to fireplace 3 Turn safety shutoff switch to the OFF position 4 Remove center brick control cover 5 Turn equipment shutoff valve clockwise to t...

Page 22: ...OPERATION 1 Turn equipment shutoff valve to ON posi tion You can now turn the burner on and off with hand held remote control unit IMPORTANT Be sure to press ON OFF buttons on hand held remote contro...

Page 23: ...rasive cleaners as this may damage glass Use a nonabra sive household glass cleaner to clean glass Do not clean glass when hot Glass must be cleaned periodically During start up it is normal for conde...

Page 24: ...l inspection of the venting system following these guidelines 1 Check areas of venting system that are exposed to the weather for corrosion rust spots or streaks and in extreme cases holes Have these...

Page 25: ...cktoseeifyouhavegas supply and that equipment shutoff valve is opened 2 Repeat lighting procedure several times to purge all air out of lines If after re peated attempts appliance does not light call...

Page 26: ...n or cor roded 1 Check electrical connec tions 1 Clean and adjust pilot flame for maximum flame im pingement on thermopile 2 Have vent system inspect ed including termination cap Remove any restrictio...

Page 27: ...ame holes blocked 3 Improper venting or exces sive blockage 4 Excessive amounts of em bers and pan material OBSERVED PROBLEM Gas odor even when gas control valve is off Gas odor during combustion Glas...

Page 28: ...www ironhaus com or www desatech com 123129 01A 28 Parts Models IDVF36SN IDVF36SP IDVF36HN IDVF36HP 10 14 9 7 21 11 32 23 24 26 25 2 8 22 15 16 17 18 19 33 34 20 30 13 1 3 4 12 6 5 27 31 29 28...

Page 29: ...1 Air Exchange 1 15 Top Insulation 1 16 120261 01 Fireplace Top 1 17 23490SA Fireplace Top Spacer 4 18 120243 01 8 Outer Pipe 1 19 111554 05 5 Inner Connector 1 20 106702 01 5 Gasket 1 21 120431 01 Bu...

Page 30: ...desatech com 123129 01A 30 Parts Burner Assembly Models IDVF36SHN IDVF36SHP IDVF36SN IDVF36SP IDVF36HN IDVF36HP 23 1 22 32 36 17 16 18 2 19 6 20 12 13 11 37 37 7 10 9 19 14 28 8 5 3 4 15 27 21 25 24...

Page 31: ...rass T Fitting 1 21 111817 06 Flextube 3 8 x 11 1 22 Burner Base Gasket 1 23 Firebox Bottom 1 24 111817 08 Flextube 3 8 x 18 1 25 120454 01 Valve Ignition Assembly 1 26 11105 Hex Screw 30 27 114365 15...

Page 32: ...www ironhaus com or www desatech com 123129 01A 32 Parts Refractory parts Models IDVF 36SN IDVF 36SP IDVF 36HN IDVF 36HP 14 20 15 19 17 13 11 6 8 4 2 1 9 5 9 1 3 7 11 12 16 18 18 22 21 10...

Page 33: ...182 01 Rear Refractory Bracket 1 11 120149 01 Refractory Housing 8 12 120148 03 Top Left Side Refractory 1 13 120148 02 Top Right Side Refractory 1 14 120148 01 Side Refractory 6 15 120146 01 Bottom L...

Page 34: ...040 When calling DESA Heating LLC have ready your name your address model and serial numbers of your heater how heater was malfunctioning purchase date Usually we will ask you to return the part to th...

Page 35: ...hase Transit damage and results from alterations are not covered by this warranty IRONHAUS disclaims all other warranties whether expressed or implied and specifically disclaims the implied warranties...

Page 36: ...proved by DESA Heating LLC Warranty parts must be obtained through authorized dealers of this prod uct and or DESA Heating LLC who will provide original factory replacement parts Failure to use origin...

Reviews: