ventinG inStALLAtiOn

NOTICE: Do not seal termination 

cap to vent pipe. Cap must be 

removable  for  vent  inspection 

and maintenance.

INSTALLATION pRECAUTIONS

•  Wear  gloves  and  safety  glasses  for 

protection

•  Use extreme caution when using ladders 

or when on roof tops

•  Be  aware  of  electrical  wiring  locations  in 

walls and ceilings

The  following  actions  will  void  the  warranty 
on your venting system:

•  Installation  of  any  damaged  venting 

component

•  Unauthorized modification of the venting sys

-

tem (Do not cut or alter vent components)

•  Installation  of  any  component  part  not 

manufactured  or  approved  by  DESA 
Heating, LLC

•  Installation  other  than  as  instructed  by 

these instructions

 

WARNING: This gas fireplace 

and  vent  assembly  must  be 

vented  directly  to  the  outside. 

The venting system must NEVER 

be attached to a chimney serv

-

ing a separate solid fuel burning 

appliance. Each direct vent gas 

appliance must use a separate 

vent  system.  Do  not  use  com

-

mon vent systems.

 

WARNING:  Vent  pipe  air 

space  clearances  to  combus

-

tibles are 1" on all sides except 

on  the  horizontal  sections, 

which  require  2"  clearances 

from the top of the pipe. Where 

the termination cap penetrates 

a combustible wall, 1" air space 

clearance is required.

NOTICE:  Read  these  instruc-

tions completely before attempt

-

ing installation.

These  models  are  tested  and  approved  for 

use with DESA Heating, LLC (direct vent) pipe 

components and terminations.
The  venting  system  must  terminate  on  the 
outside  of  the  structure  and  can  not  be  at-

tached to a chimney or flue system serving a 

separate solid fuel or gas burning appliance. 
A  direct  vent  appliance  must  have  its  own 
venting system. DO NOT common vent this 
appliance.
These  models  are  approved  to  be  vented 

either horizontally through an outside wall or 

vertically through a roof or chase enclosure 
using the following guidelines:

•  When venting system terminates horizon

-

tally  on  an  outside  wall,  you  may  install 
a  standoff  if  the  termination  cap  is  to  be 

installed  directly  on  a  combustible  finish 

such as vinyl, wood, stucco, etc.

•  Never run the vent downward as this may 

cause excessive temperatures which could 

cause a fire.

•  Vent  pipe  air  space  clearances  to  com

-

bustibles are 1" on all sides except on the 

horizontal sections, which requires 2" clear

-

ance from the top of the pipe. Where the 
termination cap penetrates a combustible 
wall, 1" air space clearance is required.

•  Have fireplace and selected vent compo

-

nents on hand to help determine the exact 
measurements when elbowing or offsetting. 

Always use wall firestops when penetrating 
walls and firestops when penetrating ceil

-

ings or attic spaces.

•  For installation of fireplace at elevations of 

4000 feet or greater, pay special attention 
to venting requirement recommendations.

 WARNING: Read all instruc-

tions completely and thoroughly 

before  attempting  installation. 

Failure to do so could result in 

serious injury, property damage 

or loss of life.

NOTICE: Failure to follow these in-

structions will void the warranty.

Summary of Contents for IRONHAUS Yellowstone IDVF36HN

Page 1: ...ierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer serv...

Page 2: ...ful home 1 Inspect your enclosure and fireplace unit for any damage Contact your dealer and or shipper immediately if damaged and document with photos etc 2 Remove handcrafted face and mesh door and s...

Page 3: ...horizontal and vertical installation This fireplace complies with the National Safety Standards This fireplace must be installed by a qualified certified or licensed service person It brings in fresh...

Page 4: ...ected annually by a qualified service person 5 You must keep control compartments burners and circulating air passages clean More frequent cleaning may be needed due to excessive lint and dust from ca...

Page 5: ...in the way of the venting system Choose a location where the heat output is not affected by drafts air conditioning ducts windows or doors Figure 2 shows some common locations Be aware of all restrict...

Page 6: ...or other materials 0 clear ance to combustible materials are for framing purpose only NOTICE Thisfireplaceisintend edforuseassupplementalheat Use this fireplace along with your primary heating system...

Page 7: ...30 cm in US if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m hori...

Page 8: ...ade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than 1 2 in size GAS VENT DIRECTLY B...

Page 9: ...vent pipe components and terminations The venting system must terminate on the outside of the structure and can not be at tached to a chimney or flue system serving a separate solid fuel or gas burnin...

Page 10: ...with special twist lock con nections Twist Lock Procedure Female ends of pipes have locking lugs indentations These lugs will slide straight into match ing slots on male ends of adjacent pipes Push pi...

Page 11: ...rior wall with provided wood screws see Figure 11 Siding standoff must sit flush against exterior fascia material 6 Connecting Vent Cap with Horizontal Vent Pipe Slide wall firestop over vent pipe bef...

Page 12: ...with critical minimum and maximum dimensions which MUST be met NOTICE Donotsealtermination cap to vent pipe Cap must be removable for vent inspection and maintenance WARNING Never run vent downward a...

Page 13: ...If area above ceiling is an insulated ceiling or an attic nail firestop from top side This prevents loose insula tion from falling into required clearance space If area above ceiling is a living space...

Page 14: ...18 shows the configurations for vertical termination Venting Installation Continued Figure 18 Vertical Venting Configuration Vertical Venting V 40 max High Altitude Installation Your DESA Heating LLC...

Page 15: ...Air Flex Vent Kit CHECK GAS TYPE Use proper gas type for the fireplace unit you are installing If you have conflicting gas types do not install fireplace See retailer where you purchased the fireplace...

Page 16: ...g equipment shutoff valve to fireplaces Figure 20 External Regulator with Vent Pointing Down Propane LP Only Propane LP Supply Tank External Regulator with Vent Pointing Down Fireplace Installation Co...

Page 17: ...ff valve was connected 3 Pressurize supply piping system by either opening propane LP supply tank valve for propane LP gas fireplace or opening main gas valve located on or near gas meter for natural...

Page 18: ...to Appliance page 22 Removing Replacing Glass Doors CAUTION Do not operate thisfireplacewithabrokenglass door panel or without the glass door panel securely in place For replacement part informa tion...

Page 19: ...ddle Bottom Brick Right Bottom Brick Glass Door Lava Rock Ember Flakes and Scrap Log Installation Lava rock ember flakes and scrap log pieces are included with your fireplace Install these items while...

Page 20: ...Once battery is activated the unit is ready to use 5 Replace center brick control cover Figure 32 Installing Battery into Back of Handset Battery Cover Back of Handset Fireplace Installation Continue...

Page 21: ...fety information col umn 1 2 Turn off all electric power to fireplace 3 Turn safety shutoff switch to the OFF position 4 Remove center brick control cover 5 Turn equipment shutoff valve clockwise to t...

Page 22: ...OPERATION 1 Turn equipment shutoff valve to ON posi tion You can now turn the burner on and off with hand held remote control unit IMPORTANT Be sure to press ON OFF buttons on hand held remote contro...

Page 23: ...rasive cleaners as this may damage glass Use a nonabra sive household glass cleaner to clean glass Do not clean glass when hot Glass must be cleaned periodically During start up it is normal for conde...

Page 24: ...l inspection of the venting system following these guidelines 1 Check areas of venting system that are exposed to the weather for corrosion rust spots or streaks and in extreme cases holes Have these...

Page 25: ...cktoseeifyouhavegas supply and that equipment shutoff valve is opened 2 Repeat lighting procedure several times to purge all air out of lines If after re peated attempts appliance does not light call...

Page 26: ...n or cor roded 1 Check electrical connec tions 1 Clean and adjust pilot flame for maximum flame im pingement on thermopile 2 Have vent system inspect ed including termination cap Remove any restrictio...

Page 27: ...ame holes blocked 3 Improper venting or exces sive blockage 4 Excessive amounts of em bers and pan material OBSERVED PROBLEM Gas odor even when gas control valve is off Gas odor during combustion Glas...

Page 28: ...www ironhaus com or www desatech com 123129 01A 28 Parts Models IDVF36SN IDVF36SP IDVF36HN IDVF36HP 10 14 9 7 21 11 32 23 24 26 25 2 8 22 15 16 17 18 19 33 34 20 30 13 1 3 4 12 6 5 27 31 29 28...

Page 29: ...1 Air Exchange 1 15 Top Insulation 1 16 120261 01 Fireplace Top 1 17 23490SA Fireplace Top Spacer 4 18 120243 01 8 Outer Pipe 1 19 111554 05 5 Inner Connector 1 20 106702 01 5 Gasket 1 21 120431 01 Bu...

Page 30: ...desatech com 123129 01A 30 Parts Burner Assembly Models IDVF36SHN IDVF36SHP IDVF36SN IDVF36SP IDVF36HN IDVF36HP 23 1 22 32 36 17 16 18 2 19 6 20 12 13 11 37 37 7 10 9 19 14 28 8 5 3 4 15 27 21 25 24...

Page 31: ...rass T Fitting 1 21 111817 06 Flextube 3 8 x 11 1 22 Burner Base Gasket 1 23 Firebox Bottom 1 24 111817 08 Flextube 3 8 x 18 1 25 120454 01 Valve Ignition Assembly 1 26 11105 Hex Screw 30 27 114365 15...

Page 32: ...www ironhaus com or www desatech com 123129 01A 32 Parts Refractory parts Models IDVF 36SN IDVF 36SP IDVF 36HN IDVF 36HP 14 20 15 19 17 13 11 6 8 4 2 1 9 5 9 1 3 7 11 12 16 18 18 22 21 10...

Page 33: ...182 01 Rear Refractory Bracket 1 11 120149 01 Refractory Housing 8 12 120148 03 Top Left Side Refractory 1 13 120148 02 Top Right Side Refractory 1 14 120148 01 Side Refractory 6 15 120146 01 Bottom L...

Page 34: ...040 When calling DESA Heating LLC have ready your name your address model and serial numbers of your heater how heater was malfunctioning purchase date Usually we will ask you to return the part to th...

Page 35: ...hase Transit damage and results from alterations are not covered by this warranty IRONHAUS disclaims all other warranties whether expressed or implied and specifically disclaims the implied warranties...

Page 36: ...proved by DESA Heating LLC Warranty parts must be obtained through authorized dealers of this prod uct and or DESA Heating LLC who will provide original factory replacement parts Failure to use origin...

Reviews: