3 - 2 5
3
Operation Modes
3.3 Hot Standby Redundancy
(Only for Dual Input & at Least Two UPSs)
7RSURYLGHFXVWRPHUVZLWKPRUHDSSOLFDWLRQFKRLFHVWKH836ZLWKGXDOLQSXWFRQ¿JXUDWLRQV
can have a hot standby redundancy function. If you use two UPSs and wish them to work
in hot standby redundancy mode, please connect the output of UPS1 to the bypass input of
UPS 2. Please see
Figure 3-23
.
For more information about the hot standby redundancy application, please contact service
personnel.
In normal condition, it is the UPS 2 inverter that supplies power to the critical loads. Both
UPS 1 & UPS 2 tri-color LEDs illuminate green.
When the UPS 2 inverter becomes abnormal, the UPS 2 will automatically transfer to
bypass mode and the UPS 1 inverter will supply power to the critical loads. Under such
circumstances, the UPS 1 tri-color LED illuminates green and the UPS 2 tri-color LED
illuminates yellow.
BYPA.
MAIN
Power Module 1
Power Module 2
Power Module...
UPS 1
MAIN
Power Module 1
Power Module 2
Power Module...
UPS 2
Q1
Inverter
Rectifier
Static Switch
Static Switch
Q5
Q2
(OFF)
(ON)
Q3
Q4
Q1
Inverter
Converter
Converter
Rectifier
Static Switch
Static Switch
Q5
Q2
(OFF)
(ON)
Q3
Q4
LOAD
(Figure 3-23: Hot Standby Redundancy Diagram (only for Dual Input & at Least Two UPSs))
Summary of Contents for Ultron DPM Series
Page 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Page 38: ......
Page 66: ......
Page 232: ......
Page 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 235: ...9 1 9 Maintenance Maintenance 9...
Page 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Page 256: ......
Page 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Page 260: ......
Page 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 264: ......