7 - 2 7
7
LCD Display & Settings
Standby
UPS-1.1
2019-Mar-01
09:30
UPS Setup
Output Setting
EVENT LOG
V
Hz
ms
Sec
(470~500)
(10~20)
(2~99)
480
60
0
10
2
Execute
Voltage
Frequency
PM Redundancy
Async Transfer Time
DC to AC Delay Time
Force Bypass to Inverter
Item
Description
Voltage
Set up the output voltage.
Frequency
Set up the output frequency as 50Hz (default) or 60Hz. The
system will automatically select the output frequency in
accordance with the bypass power.
Power Module
Redundancy
Set up how many power modules that need to be preserved
for redundancy.
Asynchronous
Transfer Time
When it is impossible for the inverter to reach synchronous
phase lock with the bypass, the output will be terminated
during conversion process according to this setup time.
DC to AC
Delay Time
Set up how much delay time the UPS needs to transfer
from Battery Mode to On-Line Mode.
Force Bypass
to Inverter
Manually force the UPS to switch from bypass to inverter
when the inverter keeps staying in the soft-start status and
is unable to transfer to On-Line mode successfully.
7.9.4 Battery Setting
Path: Main Menu
ĺ8366HWXSĺ%DWWHU\6HWWLQJ
After entering the
Battery Setting
screen
*
1
VKRZQLQWKH¿JXUHEHORZ\RXFDQVHWXSWKH
IROORZLQJLWHPV7KHVHVHWWLQJVPXVWEHFDUULHGRXWE\TXDOL¿HGVHUYLFHSHUVRQQHO3OHDVH
contact Delta customer service for assistance.
NOTE:
*
1
means that the
Administrator
password is needed. For password information,
please refer to
7.5 Password Entry
.
Summary of Contents for Ultron DPM Series
Page 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Page 38: ......
Page 66: ......
Page 232: ......
Page 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 235: ...9 1 9 Maintenance Maintenance 9...
Page 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Page 256: ......
Page 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Page 260: ......
Page 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 264: ......