4 - 1 3
4
Communication Interfaces
y
Input Breaker Detection Dry Contacts
If your external maintenance bypass cabinet’s input breaker (Q1) has the auxiliary
switch design, and you connect the auxiliary switch to the Input Breaker Detection Dry
Contacts shown in
Figure 4-19
you can monitor the input breaker’s status. If not, the
default setting of the external maintenance bypass cabinet’s input breaker (Q1) shown
on the LCD is ON.
For how to route the auxiliary switch signal cable (user-supplied), please refer to
Figure
4-12
,
Figure 4-13
,
Figure 4-14
and
Figure 4-15
.
GND
VCC
VCC
NO
NC
COM
The Auxiliary Switch of the
External Maintenance Bypass
Cabinet’s Input Breaker (Q1).
(Figure 4-19: Input Breaker Detection Dry Contacts_ Pins
’
Location and Wiring Diagram)
y
Battery Breaker Detection Dry Contacts
If your external battery cabinet’s breaker (Q5) has the auxiliary switch design, and you
connect the auxiliary switch to the Battery Breaker Detection Dry Contacts shown in
Figure 4-20
, you can monitor the status of the external battery cabinet’s breaker (Q5). If
not, the default setting of the external battery cabinet’s breaker (Q5) shown on the LCD
is ON.
For how to route the auxiliary switch signal cable (user-supplied), please refer to
Figure
4-12
,
Figure 4-13
,
Figure 4-14
and
Figure 4-15
.
Summary of Contents for Ultron DPM Series
Page 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Page 38: ......
Page 66: ......
Page 232: ......
Page 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 235: ...9 1 9 Maintenance Maintenance 9...
Page 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Page 256: ......
Page 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Page 260: ......
Page 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 264: ......