UPS Operation
3
Tap the ON/ OFF button
shown on the
Main Screen
SOHDVHVHHWKH¿JXUH
above for the button location) and the following screen will pop up to ask you if you
ZDQWWRSRZHURႇWKH836¶VLQYHUWHU3OHDVHVHOHFW
YES
'.
2019-Mar-01
09:30
UPS-1.1
AC
EVENT LOG
10 mins
Bypass
Load
0 %
Mains
10 mins
Bypass
Load
0 %
Mains
UPS-1.1
EVENT LOG
2019-Mar-01
09:30
AC
!
Are you sure to set Inverter to OFF?
Yes
No
4
After selection of '
YES
', the invert will shut down and stop running. Next, the UPS
will transfer from inverter to bypass and let the bypass source to supply power to
the connected loads, and the tri-color LED indicator will illuminate yellow.
UPS-1.1
2019-Mar-01
09:30
EVENT LOG
Bypass
10 mins
Bypass
Load
0 %
Mains
5
(a) Single Input:
Turn
ON
the external maintenance bypass cabinet’s manual bypass breaker (Q3)
and turn
OFF
the external maintenance bypass cabinet’s input breaker (Q1). Now,
the grey inverter icon
becomes green
.
At this moment, it is manual bypass to supply power to the connected loads
and the UPS begins shutdown. About 3~5 minutes, the green inverter icon
becomes grey
and the tri-color LED indicator remains yellow.
Summary of Contents for Ultron DPM Series
Page 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Page 38: ......
Page 66: ......
Page 232: ......
Page 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 235: ...9 1 9 Maintenance Maintenance 9...
Page 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Page 256: ......
Page 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Page 260: ......
Page 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 264: ......