6 - 3 6
Ultron DPM series
(b) Dual Input:
In bypass mode, the
Main Screen
shows the following diagram and the tri-color LED
indicator illuminates yellow. For the tri-color LED indicator location, please refer to
Figure 2-13
.
UPS-1.1
Bypass
2019-Mar-01
09:30
EVENT LOG
10 mins
Bypass
Load
0 %
Mains
NOTE:
For the
Main Screen
information, please refer to
7.6 Main Screen
.
2
(a) Single Input:
Switch
OFF
the external maintenance bypass cabinet’s input breaker (Q1), output
breaker (Q4) and each external battery cabinet’s breaker (Q5). After that, the LCD and
WKHWULFRORU/('LQGLFDWRUZLOOEHERWKRႇ
(b) Dual Input:
Switch
OFF
the external maintenance bypass cabinet’s input breaker (Q1), output
breaker (Q4) and each external battery cabinet’s breaker (Q5). During this time, the
tri-color LED indicator remains yellow.
Next, switch
OFF
the external maintenance bypass cabinet’s bypass breaker (Q2).
$IWHUWKDWERWKRIWKH/&'DQGWKHWULFRORU/('LQGLFDWRUZLOOEHRႇ
0DQXDO%\SDVV0RGH7XUQRႇ3URFHGXUHV
WARNING:
1. For parallel units, ensure that every operation procedure mentioned below is
synchronized to all parallel UPSs.
2. For parallel application, if you just want to operate a specific UPS but not all
parallel ones, please contact service personnel.
Summary of Contents for Ultron DPM Series
Page 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Page 38: ......
Page 66: ......
Page 232: ......
Page 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 235: ...9 1 9 Maintenance Maintenance 9...
Page 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Page 256: ......
Page 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Page 260: ......
Page 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 264: ......