3.2.6 On-Line Mode_ Dual Input_ Parallel Units
In On-Line mode (parallel), the total loads will be equally shared by parallel UPSs. If one
of the parallel units fails and its load is less than the total capacity of the remaining parallel
units, the failing UPS’s output will be switched off and its load will be equally shared by
the remaining parallel units. If the failing UPS’s load is larger than the total capacity of the
UHPDLQLQJSDUDOOHOXQLWVDOO836V¶LQYHUWHUVZLOOWXUQRႇDQGWKHWRWDOORDGVZLOOEHVXSSOLHG
by bypass power. During On-Line mode (parallel), each UPS’s tri-color LED illuminates
green and each UPS’s LCD shows the text '
AC
' in the lower right corner. Please refer to
Figure 3-18
for the path of electrical power through the parallel UPSs in On-Line mode.
MAIN
Power Module 1
Power Module 2
Power Module...
Q1
Inverter
Converter
Rectifier
Static Switch
Q5
(ON)
Q4
MAIN
Power Module 1
Power Module 2
Power Module...
Q1
Q2
Q2
Inverter
Converter
Rectifier
Static Switch
Q5
(ON)
Q4
UPS 1
UPS 2
LOAD
BYPA.
Q3
BYPA.
Q3
Static Switch
(OFF)
Static Switch
(OFF)
(Figure 3-18: On-Line Mode Diagram_ Dual Input Parallel Units)
Summary of Contents for Ultron DPM Series
Page 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Page 38: ......
Page 66: ......
Page 232: ......
Page 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 235: ...9 1 9 Maintenance Maintenance 9...
Page 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Page 256: ......
Page 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Page 260: ......
Page 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 264: ......