3 - 2 1
3
Operation Modes
3.2.8 Bypass Mode_ Dual Input_ Parallel Units
In Bypass mode (parallel), when all inverters encounter abnormal situations such as
overload, short circuit, abnormal output voltage or low battery, they will automatically shut
themselves down. Meanwhile, if all parallel UPSs detect the bypass AC source is normal,
they will automatically switch to Bypass mode to protect the connected critical loads from
power interruption. The critical loads will be equally shared by all parallel units. After the
abnormalities mentioned above are eliminated, the parallel UPSs will switch back to On-
Line mode from Bypass mode. During Bypass mode (parallel), each UPS’s tri-color LED
illuminates yellow and each UPS’s LCD shows the text '
Bypass
' in the lower right corner.
Please refer to
Figure 3-20
for the path of electrical power through the parallel UPSs in
Bypass mode.
MAIN
Power Module 1
Power Module 2
Power Module...
Q1
Inverter
Converter
Rectifier
Static Switch
Q5
(OFF)
Q4
MAIN
Power Module 1
Power Module 2
Power Module...
Q1
Q2
Q2
Inverter
Converter
Rectifier
Static Switch
Q5
(OFF)
Q4
UPS 1
UPS 2
LOAD
BYPA.
Q3
Static Switch
(ON)
Q3
Static Switch
(ON)
BYPA.
(Figure 3-20: Bypass Mode Diagram_ Dual Input Parallel Units)
Summary of Contents for Ultron DPM Series
Page 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Page 38: ......
Page 66: ......
Page 232: ......
Page 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 235: ...9 1 9 Maintenance Maintenance 9...
Page 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Page 256: ......
Page 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Page 260: ......
Page 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 264: ......