5 - 2
Ultron DPM series
5.1 Before Installation and Wiring
y
Please read this user manual thoroughly before installation, wiring and operation. Only
authorized Delta engineers or service personnel can perform installation, wiring, panel/
cover removal, maintenance and operation. If you want to execute any action men-
tioned above by yourself, the action must be under the supervision of authorized Delta
engineers or service personnel. If you use a forklift or other equipment to move the
836SOHDVHPDNHVXUHLWVORDGEHDULQJLVVXႈFLHQW3OHDVHUHIHUWR
Table 5-1
.
y
The UPS must be connected with at least an external battery cabinet (user-supplied).
Please refer to
5.5 External Battery Cabinet Connection Warnings
for relevant infor-
mation.
y
The UPS must be connected with an external maintenance bypass cabinet (user-supplied).
)RUWKHH[WHUQDOPDLQWHQDQFHE\SDVVFDELQHW¶VFRQ¿JXUDWLRQVSOHDVHUHIHUWR
1.2 Con-
nection Warnings
.
y
In this user manual, the meaning of Q1, Q2, Q3, Q4 and Q5 represents the following.
Code
Meaning
Q1
External maintenance bypass cabinet’s Input Breaker.
Q2
External maintenance bypass cabinet’s Bypass Breaker.
Q3
External maintenance bypass cabinet’s Manual Bypass Breaker.
Q4
External maintenance bypass cabinet’s Output Breaker.
Q5
External battery cabinet’s breaker.
5.2 Installation
Environment
y
Install the UPS indoors. Do not place it outdoors.
y
Make sure that transportation routes (e.g. corridors, door gates, elevators, etc.) and in-
stallation area can accommodate and bear the weight of the UPS, external maintenance
bypass cabinet (user-supplied), external battery cabinet (user-supplied) and handling
equipment. Please refer to
Table 5-1
IRUÀRRUZHLJKWORDGLQJLQIRUPDWLRQ
Table 5-1: UPS Floor Weight Loading Table
1000kW
1250kW
Weight
Weight
Loading
Weight Weight
Loading
UPS System
Cabinet
1136 lb
515 kg
83 lb/ft
2
406 kg/m
2
1169 lb
530 kg
86 lb/ft
2
418 kg/m
2
Power Modules
5521 lb
2368 kg
225 lb/ft
2
1100 kg/m
2
6527 lb
2960 kg
225 lb/ft
2
1100 kg/m
2
Summary of Contents for Ultron DPM Series
Page 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Page 38: ......
Page 66: ......
Page 232: ......
Page 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 235: ...9 1 9 Maintenance Maintenance 9...
Page 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Page 256: ......
Page 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Page 260: ......
Page 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 264: ......