4-7
4
ௐ ௐ
Communication Interfaces
No.
Event
Description
1
External input switch or breaker
detection.
Detect the external input switch or breaker’s
status (default: S1).
2
External bypass switch or
breaker detection.
Detect the external bypass switch or breaker’s
status (default: S2).
3
External output switch or
breaker detection.
Detect the external output switch or breaker’s
status (default: S3).
4
External manual bypass switch
or breaker detection.
Detect the external manual bypass switch or
breaker’s status (default: S4).
4.1.5 Output Dry Contacts
There are six sets of programmable output dry contacts (see
Figure 4-9
). Please use the
touch panel to set each dry contact as normally open (NO) or normally closed (NC). Each dry
contact can be assigned with a specific event. Six out of twenty-one events can be assigned
according to your applications. To learn how to set up, please contact your local dealer and
refer to
7.10.6 Dry Contact Setting
. For the twenty-one events, please refer to the table
below.
127(
Since the output dry contacts belong to the secondary circuit, the voltage of
each dry contact’s connected device should not exceed 60Vdc/ Vac to avoid electric
shock and insufficient insulation.
Summary of Contents for Modulon DPH 200kVA
Page 26: ...2 14 Modulon DPH Series...
Page 62: ...3 36 Modulon DPH Series...
Page 211: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 213: ...9 1 9 Maintenance Maintenance 9...
Page 215: ...10 1 10 Troubleshooting Troubleshooting 10...
Page 225: ...A1 1 Appendix 1 Technical Specifications Technical Specifications A1...
Page 228: ...A1 4 Modulon DPH Series...
Page 229: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 231: ......
Page 232: ...5013255601...