5
Use the provided four M6 screws to firmly fix the power module on the UPS.
(Figure 5-41: Fix the Power Module on the UPS)
6
Turn the power module’s switch to the upper position ( ).
(Figure 5-42: Turn the Power Module’s Switch to the Upper Position)
5.8.2 Power Module Removal
WARNING:
1. Before removing any power module, make sure that the remaining power
modules can support the connected critical loads.
2. Only qualified service personnel can perform the following removal procedures.
3. The power module is heavy (> 36 kg). At least two people are required for
handling.
1
Turn the power module’s switch to the lower position ( ). After that, the power module
will start discharging. After discharging, the power module’s LED indicator will be off.