10-2
Modulon DPH Series
When you see the following alarm messages appear on the LCD, please follow the solutions shown
below. If you see other alarm messages that are not listed in the table below, please contact Delta
service personnel for assistance. Do not perform troubleshooting if you are not trained for it.
No.
Alarm
Message
Possible Cause
Solution
1
Mains Input
Volt/ Freq Out
Range
1. The input breaker or
switch is turned off.
2. The main AC source’s
voltage or frequency is
abnormal.
1. Please check if the input breaker or switch
is turned off or not. If yes, please turn it on.
2. Please check if the main AC source’s
voltage or frequency is abnormal or not. If
yes, please wait for the main AC source to
be restored.
3. If the alarm message still exists after the
solutions mentioned above have been
executed, please contact service personnel.
2
Mains Input
Volt Phase
Seq Abnormal
The wiring is incorrect.
Please check the wiring and phase sequence
of the main AC source, and contact service
personnel for assistance.
3
Mains Input
Breaker Off
The input breaker or switch
is turned off.
1. Please check if the input breaker or switch
is turned off or not. If yes, please turn it on.
2. If the alarm message still exists after
the solution mentioned above has been
executed, please contact service personnel.
4
Bypass Input
Volt Out
Range
1. The bypass breaker or
switch is turned off.
2. The bypass AC source’s
voltage is abnormal.
1. Please check if the bypass breaker or
switch is turned off or not. If yes, please turn
it on.
2. Please check if the bypass AC source’s
voltage is abnormal or not. If yes, please
wait for the bypass AC source to be
restored.
3. If the alarm message still exists after the
solutions mentioned above have been
executed, please contact service personnel.
5
Bypass Input
Freq Out
Range
1. The bypass breaker or
switch is turned off.
2. The bypass AC source’s
frequency is abnormal.
1. Please check if the bypass breaker or
switch is turned off or not. If yes, please turn
it on.
2. Please check if the bypass AC source’s
frequency is abnormal or not. If yes,
please wait for the bypass AC source to be
restored.
3. If the alarm message still exists after the
solutions mentioned above have been
executed, please contact service personnel.
Summary of Contents for Modulon DPH 200kVA
Page 26: ...2 14 Modulon DPH Series...
Page 62: ...3 36 Modulon DPH Series...
Page 211: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 213: ...9 1 9 Maintenance Maintenance 9...
Page 215: ...10 1 10 Troubleshooting Troubleshooting 10...
Page 225: ...A1 1 Appendix 1 Technical Specifications Technical Specifications A1...
Page 228: ...A1 4 Modulon DPH Series...
Page 229: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 231: ......
Page 232: ...5013255601...