10-6
Modulon DPH Series
No.
Alarm
Message
Possible Cause
Solution
32
PM #n Fan
Abnormal
The #n power module’s fan
components are damaged.
Please contact service personnel for
assistance.
33
Replace Dust
Filter
The filter replacement date
is due.
Please contact service personnel for
assistance.
34
Parallel
Unit Config
Incompatible
- AC In Type
There are conflicts
between the parallel UPS
units’ AC input settings.
Check if the AC input settings among the
parallel UPS units are correct or not, and
contact service personnel for assistance.
35
Parallel
Unit Config
Incompatible
- Output Type
There are conflicts
between the parallel UPS
units’ output settings.
Check if the output settings among the parallel
UPS units are correct or not, and contact
service personnel for assistance.
36
Parallel
Unit Config
Incompatible
- Bat Type
1. There are conflicts
between the parallel
UPS units’ battery
settings.
2. The input dry contact
setting for the generator
is abnormal.
1. Check if the battery settings among the
parallel UPS units are correct or not, and
contact service personnel for assistance.
2. Check the input dry contact setting.
37
EXT Parallel
Comm Loss
The parallel cable is loose
or the circuit board has
abnormalities.
Check if the parallel cable is firmly connected
or not, and contact service personnel for
assistance.
38
Local Comm
Loss
The system’s internal
communication cable is
loose or the circuit board
has abnormalities.
Please contact service personnel for
assistance.
39
EXTCAN Bus
Abnormal -
Physical
The parallel cable is loose
or the circuit board has
abnormalities.
Check if the parallel cable is firmly connected
or not, and contact service personnel for
assistance.
40
INTCAN Bus
Abnormal -
Physical
The system’s internal
communication cable is
loose or the circuit board
has abnormalities.
Please contact service personnel for
assistance.
41
MONCAN
Abnormal -
Physical
The system’s internal
communication cable is
loose or the circuit board
has abnormalities.
Please contact service personnel for
assistance.
Summary of Contents for Modulon DPH 200kVA
Page 26: ...2 14 Modulon DPH Series...
Page 62: ...3 36 Modulon DPH Series...
Page 211: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 213: ...9 1 9 Maintenance Maintenance 9...
Page 215: ...10 1 10 Troubleshooting Troubleshooting 10...
Page 225: ...A1 1 Appendix 1 Technical Specifications Technical Specifications A1...
Page 228: ...A1 4 Modulon DPH Series...
Page 229: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 231: ......
Page 232: ...5013255601...