7-3
7
ௐ ௐ
LCD Display & Settings
127(
1.
*
1
indicates that the
ADMINISTRATOR
password is needed. For password information,
please refer to
7.5 Password Entry
.
2. The information on the LCD screen presented in
7. LCD Display & Settings
, including
UPS operation mode, machine number, date, time, total number of alarms, load %, battery
remaining time, user login or administrator login, are for reference only. The actual screen
of display depends on operation situation.
3. For how to turn on the touch panel, please refer to
7.2 Turning on the Touch Panel
and
7.3 ON/ OFF Button
.
7.2 Turning on the Touch Panel
127(
The UPS must be connected with a Delta or non-Delta external maintenance
bypass cabinet. The Delta external maintenance bypass cabinet is optional, and
the non-Delta external maintenance bypass cabinet is user-supplied and should
be handled and configured by Delta service personnel. For the Delta or non-Delta
external maintenance bypass cabinet’s information, please refer to
1.2 Connection
Warnings
.
1
Please refer to the following steps to turn on the touch panel.
a. Switch the bypass switch (Q0) of the UPS to the open (
ON
) position; the touch
panel will then light up and the initialization screen will appear; or
b. Turn the input breaker or switch (Q1) of the Delta or non-Delta external maintenance
bypass cabinet to the open (
ON
) position; the touch panel will then light up and the
initialization screen will appear; or
c. Turn the input breaker or switch (Q1) of the Delta or non-Delta external maintenance
bypass cabinet and the bypass switch (Q0) of the UPS to the open (
ON
) position;
the touch panel will then light up and the initialization screen will appear; or
d. Turn the external battery cabinet’s breaker (Q5) to the open (
ON
) position, open
the front door of the UPS, and press any of the battery start buttons on the
communication interfaces for 1 second and release it; the touch panel will then
light up and the initialization screen will appear. For the location of the battery start
buttons, please refer to
Figure 7-2
; for the touch panel initialization screen, please
refer to
Figure 7-3
.
Summary of Contents for Modulon DPH 200kVA
Page 26: ...2 14 Modulon DPH Series...
Page 62: ...3 36 Modulon DPH Series...
Page 211: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 213: ...9 1 9 Maintenance Maintenance 9...
Page 215: ...10 1 10 Troubleshooting Troubleshooting 10...
Page 225: ...A1 1 Appendix 1 Technical Specifications Technical Specifications A1...
Page 228: ...A1 4 Modulon DPH Series...
Page 229: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 231: ......
Page 232: ...5013255601...