6-47
6
ௐ ௐ
UPS Operation
Bypass
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
30 %
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
Power Flow
Summary
System Status
LOG IN
Administrator
10:15
May 25,2018
Administrator Login
(Figure 6-65 : Bypass Mode Screen_ Administrator Login)
5
Click
SETUP
ĺ
Mode Setting
ĺ
On-Line
. If the bypass voltage is in the normal range,
the UPS will run in bypass mode to let the bypass AC source supply power to the
output.
Bypass
UPS-1.1
MODE SETTING
MEASUREMENT
Mode Setting
SETUP
MAINTENANCE
EVENT LOG
LOG IN
Administrator
On-Line
Green
ECO
Energy
Recycle
Frequency
Conversion
Select to change system mode
10:15
May 25,2018
(Figure 6-66: Select On-Line Mode)
6
Single Input:
Switch
OFF
the UPS’s bypass switch (Q0), Delta or non-Delta external maintenance
bypass cabinet’s input breaker or switch (Q1) and output breaker or switch (Q4).
Dual Input:
Switch
OFF
the UPS’s bypass switch (Q0), Delta or non-Delta external maintenance
bypass cabinet’s input breaker or switch (Q1), bypass breaker or switch (Q2) and output
breaker or switch (Q4).
Summary of Contents for Modulon DPH 200kVA
Page 26: ...2 14 Modulon DPH Series...
Page 62: ...3 36 Modulon DPH Series...
Page 211: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 213: ...9 1 9 Maintenance Maintenance 9...
Page 215: ...10 1 10 Troubleshooting Troubleshooting 10...
Page 225: ...A1 1 Appendix 1 Technical Specifications Technical Specifications A1...
Page 228: ...A1 4 Modulon DPH Series...
Page 229: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 231: ......
Page 232: ...5013255601...