
3-32
Modulon DPH Series
3.2.14 Green Mode_ Dual Input_ Parallel Units
To activate green mode, please refer to
6.2.7 Green Mode Start-up Procedures
,
7.6 Main
Screen
and
7.10.2 Mode Setting
.
For parallel application, green mode is the same as online mode, but the difference is that
each system will automatically detect its UPS’s output status (i.e. total load capacity %) to
decide which specific power modules should be fully powered on or idle in order to achieve
higher efficiency of the UPS. During green mode, each UPS’s tri-color LED illuminates green
and each UPS’s LCD shows the text
‘Green’
in the upper right corner. Please see
Figure
3-31
for the path of electrical power through the parallel UPSs in green mode.
MAIN
LOAD
BYPA.
MAIN
BYPA.
1
2
Q0
Q2
Q0
Q2
Q1
Q4
Q3
UPS
Q1
Q4
Q3
UPS
Q5
Q5
Delta or non-Delta External Maintenance Bypass Cabinet
Batteries
Rectifier
Inverter
Static Switch
Delta or non-Delta External Maintenance Bypass Cabinet
Batteries
Rectifier
Inverter
Static Switch
(Figure 3-31: Green Mode Diagram_ Dual Input Parallel Units)
Summary of Contents for Modulon DPH 200kVA
Page 26: ...2 14 Modulon DPH Series...
Page 62: ...3 36 Modulon DPH Series...
Page 211: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 213: ...9 1 9 Maintenance Maintenance 9...
Page 215: ...10 1 10 Troubleshooting Troubleshooting 10...
Page 225: ...A1 1 Appendix 1 Technical Specifications Technical Specifications A1...
Page 228: ...A1 4 Modulon DPH Series...
Page 229: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 231: ......
Page 232: ...5013255601...