A1-2
Modulon DPH Series
Model
DPH
UPS Capacity
200kVA/
200kW
300kVA/
300kW
400kVA/
400kW
500kVA/
450kW
Power Module Q’ty
4
6
8
9
Input
Nominal Voltage
9DF9DF9DFĭ:*
Voltage Range
176 ~ 276Vac (full load)
Current Harmonic
Distortion
3%
*
1
Power Factor
> 0.99
Frequency
Range
40 ~ 70 Hz
Output
Voltage
9DF9DF9DFĭ:*
Voltage Harmonic
Distortion
0.5% (linear load)
Power Factor
1/0.9 (adjustable)
Frequency
50/60 Hz
Overload
Capability
125% : 10 minutes ;
150% : 1 minute; > 150%: 1 second
Display
10” Touch Panel
Interface
Standard
External battery temperature dry contact x 4, External
switch/ breaker status dry contact x 4,
Output dry contact x 6,
Input dry contact x 4, Parallel port x 4,
USB type A x 2, USB type B x 1,
RS-232 port x 1, MODBUS port x 1,
BMS (RJ45) x 1, Ethernet x 1,
SMART slot x 1, REPO x 1
Efficiency
Online Mode
up to 96.5%
ECO Mode
99%
Battery
Nominal Voltage
±240 Vdc
Charge Voltage
±272 Vdc (adjustable from 204 Vdc to 312 Vdc)
Protection of
Battery Deep
Discharge
Yes
Summary of Contents for Modulon DPH 200kVA
Page 26: ...2 14 Modulon DPH Series...
Page 62: ...3 36 Modulon DPH Series...
Page 211: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 213: ...9 1 9 Maintenance Maintenance 9...
Page 215: ...10 1 10 Troubleshooting Troubleshooting 10...
Page 225: ...A1 1 Appendix 1 Technical Specifications Technical Specifications A1...
Page 228: ...A1 4 Modulon DPH Series...
Page 229: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 231: ......
Page 232: ...5013255601...