3-11
3
ௐ ௐ
Operation Modes
3.1.9 Online Mode_ Single Input_ Parallel Units
In online mode (parallel), the total loads will be equally shared by the parallel UPSs. If one
of the parallel units fails and its load is less than the total capacity of the remaining parallel
units, the failing UPS’s output will be switched off and its load will be equally shared by
the remaining parallel units. If the failing UPS’s load is larger than the total capacity of the
remaining parallel units, all UPSs’ inverters will turn off and the total loads will be supplied
by bypass power. During online mode, each UPS’s tri-color LED illuminates green and each
UPS’s LCD shows the text
‘On-Line’
in the upper right corner. Please refer to
Figure 3-11
for
the path of electrical power through the parallel UPSs in online mode.
MAIN
LOAD
MAIN
1
2
Q1
Q0
Q4
Q3
UPS
Q1
Q0
Q4
Q3
UPS
ՕۋஂՕטঢҒݳષߒ
Q5
Q5
Delta or non-Delta External Maintenance Bypass Cabinet
Batteries
Rectifier
Inverter
Static Switch
Delta or non-Delta External Maintenance Bypass Cabinet
Batteries
Rectifier
Inverter
Static Switch
(Figure 3-11: Online Mode Diagram_ Single Input Parallel Units)
Summary of Contents for Modulon DPH 200kVA
Page 26: ...2 14 Modulon DPH Series...
Page 62: ...3 36 Modulon DPH Series...
Page 211: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 213: ...9 1 9 Maintenance Maintenance 9...
Page 215: ...10 1 10 Troubleshooting Troubleshooting 10...
Page 225: ...A1 1 Appendix 1 Technical Specifications Technical Specifications A1...
Page 228: ...A1 4 Modulon DPH Series...
Page 229: ...A2 1 Appendix 2 Warranty Warranty A2...
Page 231: ......
Page 232: ...5013255601...