DeviceNet Slave Communication Module IFD9502
DVP-PLC Application Manual
13
the current I/O data mapping in the PLC.
Class 0x97 Data Config
Instance0:
Attribute ID
Access rule
Name
Data type
1 Get
Revision
UINT
Instance1:
Attribute ID
Access rule
Name
Data type
Default
1 Get/Set
Reset
parameter
USINT
H’0000
2 Get/Set
M_dlen_in
UINT A
bits
3 Get/Set
D_dlen_in
UINT
6words
4 Get/Set
M_dlen_out
UINT A
bits
5 Get/Set
D_dlen_out
UINT
6words
6 Get/Set
M_in_start_adr
UINT
H’0100
7 Get/Set
D_in_start_adr
UINT
H’0198
8 Get/Set
M_out_start_adr
UINT
H’0200
9 Get/Set
D_out_start_adr
UINT
H’01F4
10 Get/Set
Comm
Timeout
UINT H’0020
3.3 When IFD9502 is connected to Delta DTA temperature controller
DTA48 48
AT
SET
PV
SV
OUT
ALM1
ALM2
°C
°F
DeviceNet
RS-485 communication
DVP28SV
DVPDNET-SL
DVPDNET
DVP28SV
RUN
STOP
Master
Delta DTA
temperature controller
1. Baud rate and the setting of communication format
Before connecting Delta temperature controller to bus, set the node address of the temperature controller as
01 and the communication format as 38,400 bps; 7, E, 1; ASCII (the format is fixed; other formats will be