DeviceNet Slave Communication Module IFD9502
DVP-PLC Application Manual
10
3.2 When IFD9502 is connected to Delta DVP series programmable logic controller
DeviceNet
RS-485 communication
Delta DVP series PLC
DVP28SV
DVPDNET-SL
DVPDNET
DVP28SV
RUN
STOP
Master
1. Baud rate and the setting of communication format
Before connecting the PLC to bus, set the node address of PLC as 01 and the communication format as
115,200 bps; 7, E, 1; ASCII (the format is fixed; other formats will be invalid).
2. Class 0x96 parameter
z
Instance0
Attribute ID
Access rule
Name
Data type
1 Get
Revision
UINT
z
Instance1 through 9
Instance ID
Description
1
S device of PLC
2
X device of PLC
3
Y device of PLC
4
M device of PLC
5
T device of PLC (bit device)
6
T device of PLC (word device)
7
C device of PLC (bit device)
8
C device of PLC (word device)
9
D device of PLC
All Instances in the table do not support any Attribute.