DeviceNet Slave Communication Module IFD9502
DVP-PLC Application Manual
8
z
Format of messages responded
Byte position
Data written into AC motor drive
Data read from AC motor drive
0
Frag [0]+XID+MAC ID
Frag [0]+XID+MAC ID
1
R/R [1]+Service code [0x10]
R/R [1]+Service code [0x0E]
2
N/A
Response data LSB
3
N/A
Response data MSB
z
Note
When modifying parameters in the parameter table of the device, make sure that the parameter allows
you to modify it before you modify it.
4. I/O data mapping (Default)
z
AC motor drive
→
DeviceNet master
Node address of
AC motor drive
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3 b2 b1 b0
H’2101
-
Status of command control
-
LED status of AC motor
drive
H’2102
Displaying frequency command
z
DeviceNet
master
→
AC motor drive
Node address of
AC motor drive
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3 b2 b1 b0
H’2000
Control command of AC motor drive
H’2001
Frequency command of AC motor drive
z
Explanation
When the equipment connected to IFD9502 is an AC motor drive, the length of data downloaded
from IFD9502 to the AC motor drive is preset as 2 words at addresses H’2000 and H’2001.
IFD9502 is able to download maximum 8 words to AC motor drive. The length of data uploaded
to IFD9502 from AC motor drive is preset as 2 words at addresses H’2101 and H’2102 and
IFD9502 is able to be uploaded maximum 8 words.
The length of data transmitted from IFD9502 to the AC motor drive is preset as 2 words. If you
need to extend the length, you have to first set up Class 0x95>>Instance1>>Attribute2 as the
destination value and next set up Attribute11 ~ Attribute 18. The length of data transmitted from
the AC motor drive to IFD9502 is preset as 2 words. If you need to extend the length, you have to
first set up Class 0x95>>Instance1>>Attribute3 as the destination value and next set up
Attribute25 ~ Attribute32.
Length of I/O data to be exchanged and address for I/O mapping can be modified through
changing Class 0x95 as listed below. The modification will be valid after IFD9502 is re-powered.
Maximum 16 words are allowed for I/O data exchange.
If you are to return the I/O mapping to default setting, change Attribute1 of Instance1 of Class
0x95 into H’0001 and re-power IFD9502. Please note that doing so can only recover the current
I/O data mapping in the AC motor drive.
Class 0x95 Data Config