DeviceNet Slave Communication Module IFD9502
DVP-PLC Application Manual
19
3.5 When IFD9502 is connected to Delta DOP-A series human machine interface
DeviceNet
RS-232/RS-485 communication
F1
F3
F2
COM1 COM2
DVP28SV
DVPDNET-SL
DVPDNET
DVP28SV
RUN
STOP
Master
Delta DOP-A HMI
1.
Baud rate and the setting of communication format
z
Before connecting the Delta HMI to bus, set the node address of HMI as 01 and the
communication format as 115,200; 7, E, 1; ASCII (the format is fixed; other formats will be
invalid).
z
When IFD9502 is connected to Delta DOP series HMI, please set up the baud rate and format
following the procedure listed below.
Open software Screen Editor and select “File>>New”. You will see the dialog box as below.
1
Follow
1
and set the Base Port Controller to “Delta DVP PLC”. Click ”OK” to create a new
file.
Select
“Options>>Configuration>>Communication” and you will see the dialog box as