DeviceNet Slave Communication Module IFD9502
DVP-PLC Application Manual
5
2.3 Address Setup Rotary Switch
The two rotary switches SW1 and SW2 set up the node address on
DeviceNet in decimal form. Setup range: 00 ~ 63 (64 ~ 99 are forbidden).
1. Example:
If you need to set the node address of IFD9502 as 26, simply switch the corresponding rotary switch of X10
1
to “2” and the corresponding rotary switch of X10
0
to “6”.
Address setting
Description
0 ~ 63
Valid DeviceNet node address
64 ~ 99
Invalid DeviceNet node address
2. Note:
The changed values on SW1 or SW2 are only valid when IFD9502 is re-powered. When IFD9502 is operating,
changing the set value of node address will be invalid.
2.4 Function Setup DIP Switch
The DIP switch SW3 is to be used on the equipment connected to
IFD9502, the selection of communication ports and setting up the baud
rate of IFD9502 and the master in DeviceNet.
1 2 3 4 5 6 7 8
SW3
DIP
ON
1. Selecting equipment connected to IFD9502
PIN 3
PIN 2
PIN 1
Equipment
Off
Off
On
AC motor drive
Off On Off Programmable
logic
controller
Off On On
Temperature
controller
On Off Off
Servo
drive
On
Off
On
Human machine interface
On On Off
Custom
equipment
On On On
Configuration
mode
z
Example
If the equipment connected to IFD9502 is Delta servo drive, you only need to switch PIN 3 in SW3 to
“On” and PIN 1 and PIN 2 to “Off” and re-power IFD9502.
z
Note:
The changed setting of DIP switch is only valid when IFD9502 is re-powered. When IFD9502 is
operating, changing the setting of DIP switch will be invalid.
2. Selecting IFD9502 communication mode
PIN 5
PIN 4
Communication mode
Off Off
RS-485
On On
RS-232
Off On
On Off
Incorrect setting