22
Part Number: 9291458 REV00 12/19
Installation
Section 2
SELF-CONTAINED REFRIGERATED DROP-IN UNITS
8100-FAP
For any non-standard installation consult the factory.
1. Install a GFCI receptacle a minimum of 14” (36cm) up
from the cabinet bottom inside the partitions. We
recommend installing a remote located power switch
for ease of use.
2. Cabinet interior minimum dimensions:
Dimension
N8131-FAP
N8144-FAP
A
30.25"/77cm
43"/109cm
B
27.75"/70cm
27.75"/70cm
C
26"/66cm
26"/66cm
D
30.25"/77cm
43"/109cm
E
25.5"/65cm
25.5”/65cm
F
Min. 2.75”/7cm - Max. 4.75”/12cm
G
12”
H
23.50”
Dimension
N8157-FAP
N8169-FAP
N8182-FAP
A
55.75"/142cm
68.5"/174cm
81.25"/206cm
B
27.75"/70cm
27.75"/70cm
27.75"/70cm
C
26"/66cm
26"/66cm
26"/66cm
D
55.75"/142cm
68.5"/174cm
81.25"/206cm
E
25.5"/65cm
25.5"/65cm
25.5"/65cm
F
Min. 2.75”/7cm - Max. 4.75”/12cm
G
15.75”
H
23.50”
3. Place the condensing unit through the counter cutout.
4. Extend the telescoping duct from the front of the
condensing unit to the back of the louver. This will
prevent recirculation of discharge air. Export models do
not have a telescoping duct, skip to step 6.
5. Put eight provided screws through the telescoping
duct side walls to hold it at the desired depth.
C
E
D
A
B
G
F
H
Use Screws to Secure Desired Depth
3 of 8 Screws Shown
6. Partitions must fully extend front to back and top to
bottom.
7. Louver cutout must extend to bottom of cabinet and
align with condenser face.
NOTE: The louver provided must be installed in front of