18
Part Number: 9291458 REV00 12/19
Installation
Section 2
SELF-CONTAINED REFRIGERATED DROP-IN UNITS
8100-EFNP, N8100BP
For any non-standard installation consult the factory.
1. Install a GFCI receptacle a minimum of 14” (36cm) up
from the cabinet bottom inside the partitions. We
recommend installing a remote located power switch
for ease of use.
2. Cabinet interior minimum dimensions:
Dimension
8148-EFNP
N8168-EFNP
8191-EFNP
A
46.87"/199cm
68.5"/174cm
90"/229cm
B
19"/48cm
19"/48cm
19"/48cm
C
26"/66cm
26"/66cm
26"/66cm
D
45.75/116cm
66.5"/169cm
90"/229cm
E
17.25"/44cm
17.25"/44cm
17.25"/44cm
F
Min. 2.75”/7cm - Max. 4.75”/12cm
Dimension
N8118BP
N8130BP
N8143BP
A
22.38"/57cm
29.75"/76cm
42.5"/108cm
B
27.75"/70cm
27.75"/70cm
27.75"/70cm
C
26"/66cm
26"/66cm
26"/66cm
D
17"/43cm
29.75"/76cm
42.5"/108cm
E
25"/64cm
25"/64cm
25"/64cm
F
Min. 2.75”/7cm - Max. 4.75”/12cm
Dimension
N8156BP
N8169BP
N8181BP
A
55.25"/140cm
68"/173cm
80.75"/205cm
B
27.75"/70cm
27.75"/70cm
27.75"/70cm
C
26"/66cm
26"/66cm
26"/66cm
D
55.25"/140cm
68"/173cm
80.75"/205cm
E
25"/64cm
25"/64cm
25"/64cm
F
Min. 2.75”/7cm - Max. 4.75”/12cm
3. Place the condensing unit through the counter cutout.
4. Extend the telescoping duct from the front of the
condensing unit to the back of the louver. This will
prevent recirculation of discharge air. Export models do
not have a telescoping duct, skip to step 6.
5. Put eight provided screws through the telescoping
duct side walls to hold it at the desired depth.
22.50”
(57cm)
C
E
D
A
B
11.50”
(29cm)
F
Use Screws to Secure Desired Depth
3 of 8 Screws Shown
6. Partitions must fully extend front to back and top to
bottom.
7. Louver cutout must extend to bottom of cabinet and
align with condenser face.
NOTE: The louver provided must be installed in front of