Used in environmentally friendly sewage treatment, water level control, drainage and
irrigation etc. Water level above 40%, Pumping in full frequency; below 40%, slow
pumping; below 10% stop pumping
Relevant Parameter Setting
Code
Recommended
Factory
Setting
Description
b00.00
65535
65535
Password of entering parameter groups. Factory set is
65535, it can be modified by b06.09
b08.01
~
b08.05
To ensure normal operation, must input parameter
according to motor nameplate
b00.02
0
x
Motor rotating direction, set according to the actual
motor wiring. Make sure the motor is running in
forward direction
6.9 Pumping Application
System Wiring
Pumpverter
Figure 12 Pumping control wiring
In diagram;
(1) Pumpverter
(2) Pumps
(3) Water Level Transmitter. Transmitter used is 4-20mA current type. Jumper for
AI1 (J19) set to current feedback signal selection I, refer to figure 1