24
b05.06
Frequenc
y upper
limit
Maximum running frequency
b05.07-
b05.05
50Hz
50Hz
b05.07
Minimum running frequency
10Hz-
b05.07Hz
Frequenc
y
lower
limit
20Hz
30Hz
b05.05
Maximu
m output
frequenc
y
10-600
Hz
50Hz
50Hz
Maximum frequency
Code
Setting
Range
Name
Description
Factory
Setting
Recommend
-ed Setting
b05.01
Low level
restart
delay
Delay time in minutes for restart after
water level switch recover
0-300min 1min
1min
0: Invalid
1: Electric contact control
S1&COM
-ON: Frequency rise
S2&COM
-ON: Frequency drop
2:Manual/Auto control
S2&COM
-OFF: Auto control
S2&COM
-ON: Manual control
3:Terminal run/stop
S1&COM
-ON: Run
S1&COM
-OFF: Stop
S2&COM
-ON: Manual control
S2&COM
-OFF: Auto control
b05.02
Terminal
S1 & S2
control
0-3
2
2
b05.03
Accelerat
ion time
0.1-
3600s
10s
Depe-
nds
on
model
Ramp up frequency
b05.04
Decceler
ation
time
0.1-
3600s
10s
Depe-
nds
on
model
Ramp up frequency