6.4 Parameter Settings for Single and Multi-Pump constrant
Pressure Control
Code
Setting
Range
Name
Description
b00.00
Debuggi
ng
Password
Retain as per the Factory default.
Can be modified by b06.09
0-65535
Factory
Setting
Recommend
-ed Setting
65535
65535
b00.01
Pressure
setting
value
S e t a c c o r d i n g t o t h e a c t u a l
requirements of the user e.g. 4 bar
0-
100 bar 3 bar
4 bar
b01.00
High
water
pressure/
Level
alarm
value
When the pressure is higher than this
preset value, the controller halts,
alarms and displays HP.
0-100
bar
8 bar
8 bar
Single pump constant pressure control
Ÿ
Set all parameters in table below on controller except b03.00-b03.09, b05.10
Multi-pump constant pressure control: One master Pump, all other
pumps slaves
Ÿ
Master controller should have pressure transducer connected
Ÿ
Set all parameters in table below for master pump controller
Ÿ
Set following parameters for slave pump controllers: b00.00, b00.02, b02.08=0,
b03.00, b03.08, b03.09, b08.01-b08.05
Multi-pump constant pressure control: One master, all other pumps
slaves with one slave set as standby master
Ÿ
Both master and standby master controllers should have pressure transmitters
connected.
Ÿ
Set all parameters in table below for master pump controller
Ÿ
Set all parameters in table below for slave pump controller that used as standby
master
Ÿ
Set following parameters for slave pump controllers: b00.00, b00.02, b02.08=0,
b03.00, b03.08, b03.09, b08.01-b08.05
Code
Setting
Range
Name
Description
Factory
Setting
Recommend
-ed Setting
b00.02
Motor
rotation
0- Forward 1- Reverse
Ensure pump motor is running in
correct direction
0-1
0
0