5. INVERTER PARAMETERS DESCRIPTION
Function
Code
Set at b06.09, default is 65535
Debugging
Password
Name
b00.00
Setting Range
Factory
Setting
Description
0~65535
65535
S e t a c c o r d i n g t o t h e a c t u a l
requirements
Pressure Setting
Valve
b00.01
0.0~100bar 3.0bar
0: Forward 1: Reverse
Ensure pump motor is running
correctly
Motor Rotating
Direction
b00.02
0~1
0
Prevention measures
0: Invalid 1: Valid
Anti-clogging
b00.04
0~1
0
Anti-clogging
Rotating Cycle
b00.05
1~300s
20.0s
Set the forward/reverse rotating
direction cycle and corresponding
output frequency of anti-clogging
(should not be higher than the rated
frequency of the pump).
Anti-clogging
Output
Frequency
b00.06
0~600
Hz
15.0Hz
When pressure is higher than the
preset value, the controller will stop
show alarms and display HP
High Water
Pressure/Level
Alarm Value
b01.00
0.0~100.0
bar
8.0bar
When the pressure is lower than the
preset value for the low pressure
running time, the controller will stop,
show alarms and displays LP
Low Water
Pressure/Level
Alarm Value
b01.01
0.0~100.0
bar
0.5bar
Low Pressure/
Level Alarm
Running Time
b01.02
0~300s
20s
Be valid when b00.03 was set to 1,
whenever sleeps, running with the
setting frequency in case of freezing
Minimum
Freeze Proofing
Frequency
b01.03
1.00-30.00
Hz
5.00Hz
When anti clogging is valid, b01.04
sets the FWD/REV transition time
Anti-clogging
FWD/REV
Dead Time
b01.04
0.0~3600s
1.0s
E.g. If the rated max. range of
transducer is 10bar, b01.05 should
be set to 10.0
Maximum
Transducer
Setting Range
b01.05
0.0~100.0
bar
10.0bar