22
b01.16
Restart
after
power on
0: Invalid 1: Valid
Allows unattended management
0-1
1
1
b01.17
Control
Mode
0: Synchronous
1: Master Slave
0-1
1
1
b02.00
PID
source
selection
0: Keypad 1:Reserved
0-1
0
0
b02.01
PID
feedback
source
selection
0: AI1 1:Reserved
0-1
0
0
b02.02
PID
Output
Characte
ristic
0: Water supply 1:Pumping
0-1
0
0
b01.05
For example, if the rated range of
transducer is 0-10 bar, b01.05
should be set to 10.0
0-100
bar
10 bar
10 bar
Maximu
m
Transduc
er
setting
range
b01.06
Lower limit settings should not be
changed unless transducer is not 4-
20mA Current Type nor 0-10V
Voltage Type.
0-10V
1.0V
1.0V
AI1 lower
limit
b01.07
-100 to
100
0%
0%
AI1 lower
limit%
b01.08
0-10V
5V
5V
AI1
higher
limit
4-20mA pressure transducer
requires setting of b01.06=1V and
b01.08=5V. When the displayed
pressure is less than the pressure
gauge reading, increase b01.08
and when the displayed pressure is
greater than pressure gauge
reading, decrease b01.08.
b01.09
100%
100%
AI1
higher
limit%
-100 to
100
Code
Setting
Range
Name
Description
Factory
Setting
Recommend
-ed Setting