28
Operation
Use case where there is a remote start/stop switch. It’s recommended to use a shielded
twisted pair cable to wire the external switch. Pump runs only when external switch S1-
COM is turned on.
Relevant Parameter Setting
According to the application use section 6.4 to set other parameters first, and then set
master b05.02=3. Auxiliaries should be put on standby by pressing run after
parameters have been set.
6.7 Manual/Auto Control Wiring and Setting
Base on above applications, connect a switch to
S2-COM
(refer to Figure 4.3.1)
Normally apply this function on auxiliaries
6.6 Terminal Start/ Stop Control Wiring and Setting
System Wiring
Figure 9 Terminal Start/Stop Wiring
In diagram:
(1) Pumpverter Intelligent Controller
(2) Pumps
(3) Air Pressure Tank
(4) Water Outlet Transducer
(5) Water Inlet Transducer
(6) Water Level Switch
(7) External Start/Stop Switch
Base on above applications, connect a switch to S1-COM refers to section 4.3