6
30
b01.02
Low pressure running time should be increased for
use-cases where water pressure rises slowly. The LP
running time b01.02 determines the maximum time
that pressure is below cut-in pressure. Controller stops
and alarms when the pressure below cut-in pressure
lasts for a duration three times of the setting b01.02.
20
xx
b05.02
Terminal S1S2 control set for pressure switch control
2
1
b01.16
Restart after power on considering unattended
management, set parameter to 1
0
x
b05.00
Water level (terminal S3) switch type according to the
switch type in use
1. NC Valid 2: NO Valid
2
x
b05.01
S3 action delay time, In case slow incoming water
leads to short run time durations
001
xxx
Acc. and Dec. time. It is recommended to set equal or
above 20s, a short acc./dec. time leads to rapid pump
cycling
b05.03
b05.04
This example uses the pressure switch for control instead of the transducer (Wiring refer
to figure 1). Adjustment of the pressure switch cut-in and cut-out pressures should be
done before running. For example for 3bar water supply, then up contact adjust above
3bar (such as at 3bar), bottom electric contact below 3bar (such as at 2.8bar).
Relevant Parameter Setting
Code
Recommended
Factory
Setting
Description
b00.00
Password of entering parameter groups. Factory set is
65535, it can be modified by b06.09
65535
65535
b02.08
All feedback lost detecting value, this application need
not pressure detect, set the parameter 0
1.0%
0.0%
b08.01
~
b08.05
Ensure normal operation must input parameter
according to nameplate of motor
b00.02
Motor rotating direction, set according to the actual
motor wiring of spot. Make sure the motor is running in
forward direction
0
x