Function
Code
Name
Setting Range
Factory
Setting
Description
0: None
Slave Quantity
b03.08
0~5
0
Fault Master Shift
•
Invalid: Factory Setting: 2
•
Valid: Master set as 0;
Slave1 set as 1
Re m a r k s : Fa u l t s h i f t r e q u i r e s
connection of backup transducer to
Slave 1. Slave 1 acts as standby
master.
Fault Shift/
Standby Master
b03.09
0~2
2
No consuming auto stop
0:Invalid 1: Valid
Sleeping
Function
b04.00
0~1
1
Delay time
Sleeping
Waiting Time
b04.01
0.0~300.0s
5.0s
Water consuming test frequency rate
Sleeping
Test
b04.02
0.0~10.0%
4.0%
During sleep the wake-up pressure
bias e.g. the setting value (L)=3.0bar,
bias (b04.03)=0.5bar, practical
pressure (P)<L-0.5=2.5bar, the
pump will restart again.
Wake up
Pressure Bias
b04.03
0.0~20.0bar 0.5bar
The pressure fluctuation which allows
sleeping
Sleeping
Bias
b04.04
0.0~1.0bar 0.0bar
Water level switch style
0: Invalid 1: NC 2: NO
Water Level
Control
b05.00
0~2
2
Delay time of restart after water level
recover
Low Level
Restart Delay
Time
b05.01
0~300min
1min
0: Invalid
1: Electric Contact Control
S1-COM on: Frequency rise
S2-COM on: Frequency drop
2. Manual/Auto Control
S2-COM off: Auto Control
S2-COM on: Manual Control
3. Terminal run/stop
S1-COM on: Run
S1-COM off: Stop
S2-COM off: Auto Control
S2-COM on: Manual Control
Terminal S1S2
Control
b05.02
0~3
2