UM-0085-B09
DT80 Range User Manual
Page 265
RG
Section Name
Key Name
Legal Values
Factory Default
Comment
SERSEN_PORT
(not present on
DT82E models)
BPS
300
,
600
,
1200
,
2400
,
4800
,
9600
,
19200
,
38400
,
57600
1200
Serial parameters for Serial Sensor port
See
DATA_BITS
7
,
8
8
STOP_BITS
1
,
2
1
PARITY
NONE
,
EVEN
,
ODD
NONE
FLOW
HARDWARE
,
SOFTWARE
,
NONE
NONE
MODE
RS232
,
RS422
,
RS485
RS232
FUNCTION
COMMAND
,
PPP
,
SERIAL
,
MODBUS
,
MODBUS_MASTER
,
DISABLE
SERIAL
Serial sensor port function:
command/PPP interface, PPP interface,
serial channel or Modbus
USB_PORT
(not present on
DT82E/82I models)
FUNCTION
COMMAND
,
PPP
,
SERIAL
,
MODBUS
,
MODBUS_MASTER
,
DISABLE
COMMAND
USB port function: command/PPP
interface, PPP interface, serial channel
or Modbus
See
HOST_MODEM
(not present on
DT8xM models)
EXT_POWER_SWITCH
NONE
,
1RELAY
,
n
DSO
,
PWR12V
NONE
Output channel used to control modem
power
DETECTION
DSR
,
ALWAYS
,
NEVER
,
WHEN_ON
DSR
Method used to detect whether modem
is present
INIT
string
AT
String to send to initialise host port
modem
MAX_CD_IDLE
0-864000
43200
(12 hours)
The number of seconds to wait while
the
DCD
signal is inactive before re-
initialising the modem (0=disable).
MODEM
(DT8xM models
only)
PIN
string
If SIM has a PIN set then it can be
entered here.
PIN_WAIT_S
0-86400
120
Max time to wait for user to enter PIN
via keypad
SERVICE
(not DT8xM2)
AUTO
,
GSM
3G
,
GSM_PREFERRED
,
3G_PREFERRED
AUTO
Specifies the network types that the
modem to which the
DT80
should
attempt to connect.
GSM_BANDS
0-7
7
Specifies the GSM bands to use
See
3G_BANDS
(not DT8xM2)
1-511
19
Specifies the 3G bands to use
See
REGISTRATION_WAIT_S 0-86400
60
Time allowed for modem to register on
mobile network
MIN_SIGNAL_FOR_DATA_
DBM
-113 - -51
(dBm)
-93
If signal level is below this then a data
connection will not be attempted and
DT80
will attempt to find a better
network.
SMS_ONLY
YES
,
NO
NO
If YES then an Internet connection will
not be established. SMS will be sent.
APN
string
(*)
Access Point Name, as specified by
mobile carrier.
APN_ACCOUNT
string
(*)
Account name if required, as specified
by mobile carrier
APN_PASSWORD
string
(*)
Account password if required, as
specified by mobile carrier
MODEM_SESSION
(DT8xM models
only)
MIN_DURATION_S
0-86400
0
Minimum communications session
duration
MAX_DURATION_S
0-86400
0
Maximum communications session
duration (hard limit, 0=disable)
MIN_IDLE_S
10-86400
120
End communications session if
communications link has been idle for
this time.
RETRY_DELAY_S
10-86400
30
Delay between session retries
TIMING_CONTROL
ALWAYS
,
CRON
,
OFF
OFF
Session will be maintained between
start and stop time, or always
START_CRON
cron-spec
0:0:12:*:*:*
If
TIMING_CONTROL=CRON
then this
specifies session start time