DKG-507 User Manual V-42
(24.05.2013)
- 45 -
Coolant Level Switch Input Configuration
PGM
Parameter Definition
Unit
Fac.Set Description
P_196
Action
0
0:
Shutdown (the engine stops immediately)
1:
Load Dump (the engine stops after cooldown)
2:
Warning (the horn relay operates)
3:
No operation
P_197
Sampling
0
0:
Always
1:
After holdoff timer
2:
When mains present
P_198
Latching
1
0:
Non latching
1:
Latching
P_199
Contact type
0
0:
Normally open
1:
Normally closed
P_200
Switching
0
0:
Battery negative
1:
Battery positive
P_201
Response delay
1
0:
No delay
1:
Delayed (4sec)
Rectifier Fail Input Configuration
PGM
Parameter Definition
Unit
Fac.Set Description
P_202
Action
2
0:
Shutdown (the engine stops immediately)
1:
Load Dump (the engine stops after cooldown)
2:
Warning (the horn relay operates)
3:
No operation
P_203
Sampling
2
0:
Always
1:
After holdoff timer
2:
When mains present
P_204
Latching
1
0:
Non latching
1:
Latching
P_205
Contact type
0
0:
Normally open
1:
Normally closed
P_206
Switching
0
0:
Battery negative
1:
Battery positive
P_207
Response delay
0
0:
No delay
1:
Delayed (4sec)
Emergency Stop Input Configuration
PGM
Parameter Definition
Unit
Fac.Set Description
P_208
Action
0
0:
Shutdown (the engine stops immediately)
1:
Load Dump (the engine stops after cooldown)
2:
Warning (the horn relay operates)
3:
No operation
P_209
Sampling
0
0:
Always
1:
After holdoff timer
2:
When mains present
P_210
Latching
0
0:
Non latching
1:
Latching
P_211
Contact type
0
0:
Normally open
1:
Normally closed
P_212
Switching
0
0:
Battery negative
1:
Battery positive
P_213
Response delay
0
0:
No delay
1:
Delayed (4sec)