DKG-507 User Manual V-42
(24.05.2013)
- 46 -
Spare
–1 Input Input Configuration
PGM
Parameter Definition Unit Fac.Set Description
P_214
Action
2
0:
Shutdown (the engine stops immediately)
1:
Load Dump (the engine stops after cooldown)
2:
Warning (the horn relay operates)
3:
No operation
P_215
Sampling
0
0:
Always
1:
After holdoff timer
2:
When mains present
P_216
Latching
0
0:
Non latching
1:
Latching
P_217
Contact type
0
0:
Normally open
1:
Normally closed
P_218
Switching
0
0:
Battery negative
1:
Battery positive
P_219
Response delay
0
0:
No delay
1:
Delayed (4sec)
Spare-2 Input Input Configuration
PGM
Parameter Definition Unit Fac.Set Description
P_220
Action
2
0:
Shutdown (the engine stops immediately)
1:
Load Dump (the engine stops after cooldown)
2:
Warning (the horn relay operates)
3:
No operation
P_221
Sampling
0
0:
Always
1:
After holdoff timer
2:
When mains present
P_222
Latching
0
0:
Non latching
1:
Latching
P_223
Contact type
0
0:
Normally open
1:
Normally closed
P_224
Switching
0
0:
Battery negative
1:
Battery positive
P_225
Response delay
0
0:
No delay
1:
Delayed (4sec)