DKG-507 User Manual V-42
(24.05.2013)
- 39 -
PGM
Parameter Definition
Unit
Fact.Set Description
P_087
Exercise Day and
Time
-
168
This parameter defines the start day and hour of
the exerciser.
Values higher or equal to 168 mean that the
exerciser is off.
The exercise may be selected to start at the
beginning of the any hour of the week. The
parameter value is the hour count of the start time.
Examples:
0 = exercise starts at Monday 00:00
8 = exercise starts at Monday 08:00
24 = exercise starts at Tuesday 00:00
167 = exercise starts at Sunday 23:00
168 = exerciser off
If a daily exercise is selected, then the day
information is don’t care and the exercise will be
performed every day regardless of the day
selection.
If the monthly exerciser is selected, then the
exercise will be performed during the first 7 days
of each month at the programmed day and hour.
P_088
Exercise Duration
min
10
This parameter defines the exercise duration and
programmed in 10 minute steps up to 24 hours.
P_089
Exercise Off/On Load
-
0
0:
Exercise at
TEST
mode
1:
Exercise at
LOAD TEST
mode
P_090
Exercise Period
-
1
0:
exercise every day (the exercise will be
performed every day regardless of the day
selection of Exercise Dat and Time parameter).
1:
exercise once per week
2:
exercise once per month (the exercise will be
performed during the first 7 days of each month at
the programmed day and hour).
P_091
Language Selection
-
0
This is the language used in SMS messages.
0:
english
1:
turkish
2:
french
3:
russian
P_092
Secondary Volt/Freq
-
0
0:
Use primary voltage/frequency limits
1:
When signal is applied to the SPARE-1 input,
use secondary voltage/frequency limits
P_093
Engine Control Only
-
0
0: Genset control
1: Engine control (no alternator