D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 60 -
ALARM #
LOADDUMP#
WARNING#
DESCRIPTION
68
324
580
J1939 ECU FAIL:
Set if no information has been received during
Message
Absence Timer
from the ECU of the electronic engine.
This fault condition is only controlled when fuel is on.
69
325
581
OVERCURRENT:
Set if at least one of the genset phase currents goes over
the
Overcurrent Limit
for the period allowed by the IDMT
curve setting. The allowed timer is dependent of the
overcurrent level. If currents go below the limit before
expiration of the timer then no alarm will be set. Please
check chapter
Overcurrent Protection (IDMT)
for more
details.
70
326
582
OVERLOAD:
Set if the genset power (kW) supplied to the load goes over
the
Overload
limit for
Overload Timer
. If the power goes
below the limit before expiration of the timer then no alarm
will be set.
71
327
583
REVERSE POWER:
Set if the genset power (kW) is negative and goes over the
Reverse Power
limit for
Reverse Power Timer
. If the
power goes below the limit before expiration of the timer
then no alarm will be set.
72
328
584
GENSET PHASE ORDER FAIL:
Set if the fault is enabled and the genset phase order is
reverse.
73
329
585
MAINS PHASE ORDER FAIL:
Set if the fault is enabled and the mains phase order is
reverse.
74
330
586
GENSET CB FAIL TO CLOSE:
Set if the feedback input is defined and the related
contactor block feedback signal is not detected after the
expiration of Contactor Open/Close Fail Timer.
75
331
587
GENSET CB FAIL TO OPEN:
Set if the feedback input is defined and the related
contactor block feedback signal is not detected after the
expiration of Contactor Open/Close Fail Timer.
76
332
588
MAINS CB FAIL TO CLOSE:
Set if the feedback input is defined and the related
contactor block feedback signal is not detected after the
expiration of Contactor Open/Close Fail Timer.
77
333
589
MAINS CB FAIL TO OPEN:
Set if the feedback input is defined and the related
contactor block feedback signal is not detected after the
expiration of Contactor Open/Close Fail Timer.
78
334
590
SERVICE-1 REQUEST:
Set if at least one of the service-1 counters has expired.
In order to reset the service counters please hold pressed
both
and
buttons during 5 seconds. The screen
will displ
ay “Completed!”
Summary of Contents for D-100 MK2
Page 37: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 37 6 3 ATS FUNCTIONALITY ...
Page 38: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 38 6 4 REMOTE START FUNCTIONALITY ...
Page 39: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 39 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 40: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 40 6 6 ...