D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 52 -
STOPPING THE ENGINE:
Press STOP
button
STARTING THE ENGINE:
Press RUN
button
LOAD TEST:
Hold pressed RUN
button for 5 seconds. The genset will run and take the load.
AUTOMATIC OPERATION:
Press AUTO
button. Check that
AUTO READY
led is illuminated.
The STOP mode is entered by pressing the
button.
In this mode, the genset will be in a rest state.
When STOP mode is selected, if the genset is running under load, then it will be immediately unloaded. The
engine will continue to run during
Cooldown Timer
and will stop afterwards.
If the STOP button is pressed again, then the engine will immediately stop.
If the engine fails to stop after the expiration of
Stop Timer
then a
Fail to Stop
warning will occur.
In this mode, the mains contactor will be energized only if mains phase voltages and frequency are within the
programmed limits. If enabled, the mains phase order is also checked.
If a
Remote Start
or
Force to Start
signal arrives in STOP mode, the genset will not start until AUTO mode
is selected.
Mode can be changed anytime without negative effect.
Changing the operation mode while the genset is running will
result into a behavior suitable for the new operating mode.
13.2. STOP MODE
13.1. QUICK START GUIDE
13. OPERATION OF THE UNIT
Summary of Contents for D-100 MK2
Page 37: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 37 6 3 ATS FUNCTIONALITY ...
Page 38: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 38 6 4 REMOTE START FUNCTIONALITY ...
Page 39: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 39 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 40: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 40 6 6 ...