D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 65 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
001-LCD Contrast
-
30
50
31
This parameter is used to set LCD
contrast. Adjust for the best viewing
angle.
002-Fault Holdoff Timer
sec
0
120
12
This parameter defines the delay after
the engine runs and before the fault
monitoring is enabled.
003-Alarm Relay Timer
sec
0
120
60
This is the period during which the
ALARM relay is active. If the period is
set to 0, this will mean that the period is
unlimited.
004-Emergency Backup
Operation
-
0
1
0
0: In RUN mode, the load will not be
transferred to the genset even if the
mains fails.
1: In RUN mode, the load will be
transferred to the genset if the mains
fails.
005-Exercise Time
-
006-Exercise Period
-
0
1
0
0: exercise once per week
1: exercise once per month
The exact exerciser day and time is
adjusted within the EXERCISE
SCHEDULE section.
007-Exercise Off/On
Load
-
0
1
1
0: Exercise at RUN mode
1: Exercise at TEST mode
008-Delayed Simulate
Mains
-
0
1
0
0: delayed simulate mains disabled
1: delayed simulate mains enabled
009-SMS Enable
-
0
1
0
0: SMS messages disabled
1: SMS messages enabled
010-GPRS Connection
Enable
-
0
1
0
0: GPRS disabled
1: GPRS enabled
011-Rainbow Scada
Refresh Rate
sec
0
65535
5
The unit will update the distant
monitoring terminal with this rate.
012-Rainbow Scada
Address-1 Port
-
0
65535
0
This is the port number of the first
monitoring terminal address.
013-Rainbow Scada
Address-2 Port
-
0
65535
0
This is the port number of the second
monitoring terminal address.
014-Modbus Address
-
0
240
1
This is the modbus controller identity
used in Modbus communication.
015-Oil Pressure Switch
Priority
-
0
1
0
0: crank cut is performed through oil
pressure switch and oil pressure sender
reading
1: crank cut is performed only through
oil pressure switch
016-Flashing Relay ON
Timer
min
0
1200
0
Delayed Simulate Mains Operation:
max genset running time after Simulate
Mains signal disappears.
Dual Genset Systems: flashing relay
ON state duration timer.
017-Flashing Relay OFF
Timer
min
0
1200
0
Dual Genset Systems: flashing relay
OFF state duration.
16. PROGRAM PARAMETER LIST
Summary of Contents for D-100 MK2
Page 37: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 37 6 3 ATS FUNCTIONALITY ...
Page 38: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 38 6 4 REMOTE START FUNCTIONALITY ...
Page 39: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 39 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 40: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 40 6 6 ...