D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 76 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
144-Gas Solenoid Delay
sec
0
240
5
The gas solenoid of the gas engine (if
assigned by
Relay Definitions
) will be
opened after this delay during cranking.
145-Crank Cut Voltage
V-AC
0
65000
100
The crank relay output is deenergized
when the genset phase L1 voltage
reaches this limit.
146-Crank Cut
Frequency
Hz
0
100
10
The crank relay output is deenergized
when the genset frequency reaches this
limit.
147-Crank Cut RPM
rpm
0
65000
500
The crank relay output is deenergized
when the engine rpm reaches this limit.
148-Crank Cut Charge
Voltage
V-DC
0
40
6
The crank relay output is deenergized
when the charge alternator voltage
reaches this limit.
149-Crank Cut with Oil
Pressure
-
0
1
0
0:
no crank cut with oil pressure
1:
cranking is cut when oil pressure
switch is open or the oil pressure
measured is above shutdown limit.
150-Crank Cut with Oil
Pressure Delay
sec
0
30
2
If crank cutting with oil pressure is
enabled, cranking is cut after this delay
when oil pressure switch is open or the
oil pressure measured is above
shutdown limit.
151-Charge Input
Connected
-
0
1
0
0:
Crank cutting with charge input
disabled
1:
Crank cutting with charge input
enabled
152-Fuel Tank Capacity
Lt
0
65000
0
The full capacity of the fuel tank. If this
parameter is zero, the fuel quantity in
the tank is not displayed.
153-Fuel Consumption
per Hour
%
0
100
0.0
This parameter is the threshold for
sending FUEL THEFT and FUELLING
sms messages.
If this parameter is set to 0, then no
Fuel Theft and Fuelling sms messages
will be sent.
If SMS is required, set this parameter to
a value above the hourly fuel
consumption of the genset.
154-Coolant Cooler On
°C
0
250
90
If the coolant temp is above this limit then
the cooler relay function will become
active.
155-Coolant Cooler Off
°C
0
250
80
If the coolant temp is below this limit then
the cooler relay function will become
inactive.
156-Coolant Heater On
°C
0
250
50
If the coolant temp is below this limit then
the heater relay function will become
active.
157-Coolant Heater Off
°C
0
250
60
If the coolant temp is above this limit then
the heater relay function will become
inactive.
158-Fan Overrun Timer
sec
0
240
0
The cooler relay will stay active during
this timer after the coolant temp is below
“Coolant Cooler Off” limit.
Summary of Contents for D-100 MK2
Page 37: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 37 6 3 ATS FUNCTIONALITY ...
Page 38: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 38 6 4 REMOTE START FUNCTIONALITY ...
Page 39: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 39 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 40: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 40 6 6 ...