D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 61 -
ALARM #
LOADDUMP#
WARNING#
DESCRIPTION
79
335
591
SERVICE-2 REQUEST:
Set if at least one of the service-2 counters has expired.
In order to reset the service counters please hold pressed
both
and
buttons during 5 seconds. The screen
will display “Completed!”
80
336
592
SERVICE-3 REQUEST:
Set if at least one of the service-3 counters has expired.
In order to reset the service counters please hold pressed
both
and
buttons during 5 seconds. The screen
will display “Completed!”
81
337
593
ENGINE RUNNING:
Set if the engine is running while the fuel output is not
energized.
82
338
594
AUTO NOT READY:
Set if the genset is not in AUTO mode or a fault condition
or the weekly schedule prevents the automatic starting of
the genset.
FUEL THEFT
Engine is not running:
If the fuel level measured from the sender input falls by 20% or more in
one hour, then
Fuel Theft
warning occurs (the detection delay is 10 sec,
not adjustable).
Engine is running:
If the fuel level measured from the sender input falls by 2x”
hourly fuel
consumption percentage
” or more, then
Fuel Theft
warning occurs.
FUEL FILLING
If the fuel level measured from the sender input is increased by 20% or
more in one hour, then
Fuel Filling
non-visual warning occurs (the
detection delay is 10 seconds, not adjustable).
MAINTENANCE DONE
Sent when the periodic maintenance counters are manually reset.
These warnings are not announced at the device front panel,
however they appear in event logs, transferred to the Scada and
cause SMS sending.
13.4. NON-VISUAL WARNINGS
Summary of Contents for D-100 MK2
Page 37: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 37 6 3 ATS FUNCTIONALITY ...
Page 38: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 38 6 4 REMOTE START FUNCTIONALITY ...
Page 39: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 39 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 40: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 40 6 6 ...