D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 79 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
171-J1939 Speed Adjust
%
-100
+100
0.0
This parameter adjusts the speed of an
ECU controlled engine by +/- 8%.
172-Battery Charge Run
Voltage
V-DC
0
35.0
0
If the battery voltage goes below this
limit the engine will be automatically
started in order to charge the battery
using the charge alternator.
173-Battery Charge Run
Timer
min
0
1200
0
If the battery voltage goes below the
Battery Charge Run Voltage limit, the
engine will be automatically run during
this period in order to charge the battery
using the charge alternator.
174-J1939 Message
Suspand Timer
sec
0
240
3
After a crank start, messages coming
from the ECU are ignored during this
timer.
175-J1939 Message
Absence Timer
sec
0
240
3
If no message is received from the ECU
during this timer, then an ECU Fail
Alarm is generated.
176-Oil Pump Stop
Pressure
bars
0
20
0
The oil pump is activated prior to the
crank cycle and stopped when this
pressure level is reached.
If this value is set to zero, then the oil
pump is not activated.
177-Disable ECU speed
control
-
0
1
0
0:
Engine speeed checking is
performed with the RPM information
coming from the engine ECU unit.
1:
the RPM information coming from the
engine ECU unit is not used for engine
speed checking.
178-J1939 SPN Mask
-
0
65535
0
The SPN number written to this
parameter is excuded from engine ECU
alarm list.
179-J1939 FMI Mask
-
0
65535
0
The FMI number written to this
parameter is excuded from engine ECU
alarm list
180-J1939 Speed toggle
-
0
1
0
For Volvo engines, when this parameter
is set to 1, then the speed of the engine
is switched between 1500 and 1800
rpm.
181-RTC Date
-
01
31
Current day of the month.
182-RTC Month
-
01
12
Current month.
183-RTC Year
-
00
99
Last two digits of the current year.
184-RTC Hours
-
00
23
Current hour of the day.
185-RTC Minutes
-
00
59
Current minute of the hour.
186-RTC Seconds
-
00
59
Current second of the minute.
Summary of Contents for D-100 MK2
Page 37: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 37 6 3 ATS FUNCTIONALITY ...
Page 38: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 38 6 4 REMOTE START FUNCTIONALITY ...
Page 39: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 39 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 40: ...D 100 MK2 User Manual Firmware V 6 3 K96D01 EN 40 6 6 ...