LANcat
User Manual
Page 3-2
Running Autotest
TWO-WAY SYSTEM
1.
Connect one end of cable to the main unit and the other end to
the Remote Unit.
2.
Set the Remote Unit’s dial to REMOTE.
3.
Set the Main Unit’s dial to AUTOTEST. The test runs
automatically, then displays the results.(Press the arrow
keys to change the cable test standard).
4.
Press START (F1) to re-start Autotest. Press VIEW (F3) to
review Autotest test results.
5.
Press SAVE (F4) or ENTER to save the Autotest test results.
6.
Press TALK (F2) to ring the Remote Unit at the other end.
ONE-WAY SYSTEM
1.
Connect one end of cable to the LANcat and the other end to the
Remote Unit.
2.
Set dial to AUTOTEST. The test runs automatically then
displays the results. (Press the arrow keys to change the cable
test standard).
3.
Press START (F1) to re-start Autotest. Press VIEW (F3) to
review Autotest test results.
4.
Press SAVE (F4) or ENTER to save the Autotest test results.