44
Technical data
Unit
The below table gives the technical data of the HRV 5.
Specification
Unit
Value
Voltage, frequency
V/Hz
1 × 230 V/50/60 Hz ± 10 %
Max. power consumption with/without heat-
ing element
W
900/270
Operating range
°C
÷ 20 til + 50
Installation range
°C
+ 10 til + 40
Dimensions, W × H × D
mm
592 × 820 × 582
Dimensions, packaging, W × H × D
mm
622 × 850 × 600
Weight
kg
55
Weight incl. packaging
kg
60
Cabinet, hot galvanized sheet steel
mm
0.9
Colour
RAL
9016 (hvid)
Filter sizes
F7 (supply air)
G4 (extract air)
mm
300 × 300 × 48
400 × 240 × 48
Rotary heat exchanger
-
Aluminium
Heat recovery efficiency, dry, balanced air
volume
%
Up to 80
IP
-
44
Fire resistance of insulation material
-
DIN 4102 B2
Noise level - 1 m away from the cabinet
@ the given fan speeds
dB(A)
n = 1000 rpm: 43,6
n = 1500 rpm: 45,7
n = 2000 rpm: 49,8
Remote controller
The below table gives the technical data of the remote controller for HRV 5.
Specification
Unit
Value
Wireless radio communication
MHz
868,4
Output power
-
< 25 mW, < 1 % duty cycle
Operating range,
non-condensing (< 95 % RH)
° C
÷ 20 to + 50
Storage without batteries,
non-condensing (< 95 % RH)
° C
÷ 20 to + 70
Summary of Contents for HRV 5
Page 1: ...Focus Trust Initiative HRV 5 Service manual DA GB DE No 039994 rev 2 0 08 03 2011...
Page 2: ...2005 layout...
Page 3: ...HRV 5 Service manual EN DA DE No 039994 rev 2 0 08 03 2011...
Page 54: ...52...
Page 104: ...52...
Page 138: ...36 Fortsetzung auf der n chsten Seite...
Page 148: ...46 Abmessungen Abbildung Die Abbildung zeigt die Abmessungen eines HRV 5...
Page 154: ...52 Firmenstempel Datum und Unterschrift...
Page 157: ...2005 layout...